Verified by manufacturer 6 days ago
CoolStream S
Evaporative cooler consisting of a mixed air module, a fan module and an evaporative cooling module.
Can be roof- or ground-mounted to suit site constraints.
CoolStream A provides maximum design flexibility through three individual modules: the evaporative cooling module, the mixed air module, and the fan module. Similar to the CoolStream T, it blends fresh outdoor air with the warm recirculated air inside the building, ensuring effective mixing of supply air with the air just beneath the ceiling. The individual modules of a CoolStream A system can be positioned in many places, allowing maximum flexibility.
Product Highlights:
CoolStream A – Flexible Modular Cooling & Recirculation
Product Technical Information:
Connection variants:
In the classic version, the CoolStream A (cooling module) is installed on the roof with a bottom duct connection. The cooled supply air is introduced into the room using the Coltair ventilation system. A side duct connection is typically used is when the unit is installed next to a building. If the unit is placed on the floor, the supply air is first conveyed upwards. In this instance a top duct connection is used.
Fans:
For applications with low pressure drops, particularly quiet axial fans are available, while centrifugal fans are also suitable for higher filter classes and external pressures. Only premium EC fans are used in CoolStream systems. Please contact our technical team to discuss your requirements further.
Optional outdoor air filter:
Heat reclaim:
Performance classes:
Controls:
Power supply:
380-415V / 50 Hz / 3~ + N + PE.
Classification data | |
Duty | |
Air volume | Manufacturer's standard. Guidance for specification option: See Fan types guidance for values. |
Components | |
Filters | Single stage: Z-line filter class G4. Single stage: Z-line filter class M5. Single stage: Z-line filter class F7. Two stage: Z-line filter G2+F9. |
Fans | |
Fan type | Axial, type 12A. Guidance for specification option: Airflow (without filters): Up to 3.3 m³/s (12 000 m³/h). Axial, type 17A. Guidance for specification option: Airflow (without filters): Up to 4.7 m³/s (17 500 m³/h). Axial, type 22A. Guidance for specification option: Airflow (without filters): Up to 6.1 m³/s (22 000 m³/h). Axial, type 30A. Guidance for specification option: Airflow (without filters): Up to 8.3 m³/s (29 750 m³/h). Centrifugal, type 12C. Guidance for specification option: Airflow (without filters): Up to 3.3 m³/s (11 750 m³/h). Centrifugal, type 16C. Guidance for specification option: Airflow (without filters): Up to 4.5 m³/s (16 250 m³/h). Centrifugal, type 23C. Guidance for specification option: Airflow (without filters): Up to 6.3 m³/s (22 500 m³/h). Centrifugal, type 29C. Guidance for specification option: Airflow (without filters): Up to 8.1 m³/s (29 950 m³/h). |
Accessories | None. Coltair inflow unit. Guidance for specification option: Used in combination with the CoolStream unit to provide ventilation, heating and heat reclaim. Side panel with insect guard. Side panel with G4 filter. Guidance for specification option: In accordance with EN 779:2012. Side panel with M5 filter. Guidance for specification option: In accordance with EN 779:2012. Side panel with F7 filter. Guidance for specification option: In accordance with EN 779:2012. "All Seasons" option. Guidance for specification option: For ventilation, heat recovery and cooling throughout the year. VDI certification. Guidance for specification option: Other options include internal lighting / light switch, sight glass, pressure display (only when filters are supplied), VDI 6022 certificate. Consult manufacturer for details and insert requirements. |
Controls | Colt Cortiva controller via browser or app. |
Connection | Bottom duct connection. Guidance for specification option: For use when installed on to the roof. Side duct connection. Guidance for specification option: For use when combined with alternative HVAC equipment to the standard Coltair arrangement. Top duct connection. Guidance for specification option: For use when adjacent to a building. |
System types | CoolStream S. Guidance for specification option: Highly efficient adiabatic system, using the principle of evaporative cooling to provide cooled air as part of a balanced ventilation system, in situations where conventional air conditioning is not cost-effective.
|