Verified by manufacturer 5 months ago
1000 x 1250 mm ventilator, aluminium lid
Flap ventilator, suitable for roof access and smoke control.
Combined AOV smoke ventilator and roof access hatch designed providing either 1.0 or 1.5 m² measured free area in accordance with Approved Document B, Appendix C.
Suitable for use as a staircase ventilator or roof mounted lobby/ corridor ventilator and to provide external roof access.
A combined AOV smoke ventilator and roof access hatch designed providing either 1.0 or 1.5 m² measured free area in accordance with Approved Document B, Appendix C.
It is suitable for use as a staircase ventilator or roof mounted lobby/ corridor ventilator and to provide external roof access.
Features and benefits:
Color | Silver Guidance for specification option: Standard (mill finish). Other Guidance for specification option: RAL colour. |
Finish | Mill finish Powder-coated Guidance for specification option: Polyester powder-coated. |
Material | Aluminium Stainless steel EPDM |
Shape | Rectangle |
Length | 1350 mm 1600 mm |
Width | 1600 mm 1850 mm |
Height | 398 mm |
Uniclass | |
CAWS | L10/45 Rooflights L10/460 Rooflights L10/47 Roof ventilators L10/490 Roof ventilators |
Product range |
Opening type | B. |
Mounting | Roof-mounted. |
Aerodynamic free area | 1.0 m². |
Reliability classification | Re 50.Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. Watertightness: Rain defence tested to 75 m/h (at 13 m/s). Sound insulation: <29 dB Rw. |
Snow load classification | 250 N/m².Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. |
Low ambient temperature classification | T (-05).Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. |
Wind load classification | WL 1500.Guidance for specification option: 1500 N/m². Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. Air permeability (to BS EN 12207): Class 4. |
Resistance to heat classification | B300.Guidance for specification option: Resistance to fire (to BS EN 13501-1): E. Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. |
Arrangement | Insulated aluminium panel.Polycarbonate panel. |
Dimensions | |
Length | 1600 mm.Guidance for specification option: Overall length. |
Width | 1350 mm.Guidance for specification option: Overall width. |
Height | 398 mm. |
Controls | 24 V d.c. linear actuator (drive in/ drive out).Guidance for specification option: Motor: 2.6 A; 62.4 W; 1550 N. Manufacturer guidanceMounted on a pivoting carriage capable of opening the lid to the fire position of 140° from the horizontal within 60 seconds and of re-closing it. |
Materials | |
Ventilator | |
Frame | Aluminium.Guidance for specification option: Thermally broken aluminium frame with continuous seals for excellent airtightness. Opens to 140° from the horizontal. |
Glazing | As arrangement. |
Finish | Mill finish.Polyester powder-coated.Guidance for specification option: Insert colour requirements below. Standard 40 µm. |
Colour | Silver.Guidance for specification option: Standard for mill finish. RAL.Guidance for specification option: Many colour options available; consult manufacturer for details and insert requirements. |
Integral upstands | |
Material | Manufacturer's standard.Guidance for specification option: Thermally broken, 40 mm-thick welded insulated and thermally broken aluminium. EN AW-6063 T6 (extrusion) and EN AW-3005 H14 (sheet) aluminium alloy. |
Finish | As ventilator.Mill finish.Polyester powder-coated.Guidance for specification option: Insert colour requirements below. Standard 40 µm. |
Colour | As ventilator.Silver.Guidance for specification option: Standard for mill finish. RAL.Guidance for specification option: Many colour options available; consult manufacturer for details and insert requirements. |
Seals | EPDM profiles.Guidance for specification option: Keeps air leakage down to a minimum. |
U-value | Up to 1.3 W/m²K. |
Fixing | Fixing flange for curb. Guidance for specification option: Installation angle must be at 0° (horizontal). |