Verified by manufacturer 6 months ago
1000 x 1250 mm ventilator, aluminium lid
Flap ventilator, suitable for roof access and smoke control.
Combined AOV smoke ventilator and roof access hatch designed providing either 1.0 or 1.5 m² measured free area in accordance with Approved Document B, Appendix C.
Suitable for use as a staircase ventilator or roof mounted lobby/ corridor ventilator and to provide external roof access.
A combined AOV smoke ventilator and roof access hatch designed providing either 1.0 or 1.5 m² measured free area in accordance with Approved Document B, Appendix C.
It is suitable for use as a staircase ventilator or roof mounted lobby/ corridor ventilator and to provide external roof access.
Features and benefits:
Color | Silver Guidance for specification option: Standard (mill finish). Other Guidance for specification option: RAL colour. |
Finish | Mill finish Powder-coated Guidance for specification option: Polyester powder-coated. |
Material | Aluminium Stainless steel EPDM |
Shape | Rectangle |
Length | 1350 mm 1600 mm |
Width | 1600 mm 1850 mm |
Height | 398 mm |
Uniclass | |
CAWS | L10/45 Rooflights L10/460 Rooflights L10/47 Roof ventilators L10/490 Roof ventilators |
Product range |
Opening type | B. |
Mounting | Roof-mounted. |
Aerodynamic free area | 1.0 m². |
Reliability classification | Re 50.Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. Watertightness: Rain defence tested to 75 m/h (at 13 m/s). Sound insulation: <29 dB Rw. |
Snow load classification | 250 N/m².Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. |
Low ambient temperature classification | T (-05).Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. |
Wind load classification | WL 1500.Guidance for specification option: 1500 N/m². Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. Air permeability (to BS EN 12207): Class 4. |
Resistance to heat classification | B300.Guidance for specification option: Resistance to fire (to BS EN 13501-1): E. Manufacturer guidancePerformance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type. |
Arrangement | Insulated aluminium panel.Polycarbonate panel. |
Dimensions | |
Length | 1600 mm.Guidance for specification option: Overall length. |
Width | 1350 mm.Guidance for specification option: Overall width. |
Height | 398 mm. |
Controls | 24 V d.c. linear actuator (drive in/ drive out).Guidance for specification option: Motor: 2.6 A; 62.4 W; 1550 N. Manufacturer guidanceMounted on a pivoting carriage capable of opening the lid to the fire position of 140° from the horizontal within 60 seconds and of re-closing it. |
Materials | |
Ventilator | |
Frame | Aluminium.Guidance for specification option: Thermally broken aluminium frame with continuous seals for excellent airtightness. Opens to 140° from the horizontal. |
Glazing | As arrangement. |
Finish | Mill finish.Polyester powder-coated.Guidance for specification option: Insert colour requirements below. Standard 40 µm. |
Colour | Silver.Guidance for specification option: Standard for mill finish. RAL.Guidance for specification option: Many colour options available; consult manufacturer for details and insert requirements. |
Integral upstands | |
Material | Manufacturer's standard.Guidance for specification option: Thermally broken, 40 mm-thick welded insulated and thermally broken aluminium. EN AW-6063 T6 (extrusion) and EN AW-3005 H14 (sheet) aluminium alloy. |
Finish | As ventilator.Mill finish.Polyester powder-coated.Guidance for specification option: Insert colour requirements below. Standard 40 µm. |
Colour | As ventilator.Silver.Guidance for specification option: Standard for mill finish. RAL.Guidance for specification option: Many colour options available; consult manufacturer for details and insert requirements. |
Seals | EPDM profiles.Guidance for specification option: Keeps air leakage down to a minimum. |
U-value | Up to 1.3 W/m²K. |
Fixing | Fixing flange for curb. Guidance for specification option: Installation angle must be at 0° (horizontal). |
Airlite Highly Insulated Natural Louvred Ventilator
Apollo / Apollo ATI natural flap roof ventilators
Colt Seefire Ventilator For Stairwells
Coltlite Glazed and Insulated Natural Louvred Ventilators
ECO Seefire Natural Louvred Ventilator
FCO Façade Ventilator
Firelight DUO Natural Twin Flap Roof Ventilator
Firelight FL2 Natural Flap Ventilator
Firelight FL3 High Performance Natural Flap Ventilator
Kameleon 5E Natural Casement Ventilator