Application

Combined AOV smoke ventilator and roof access hatch designed providing either 1.0 or 1.5 m² measured free area in accordance with Approved Document B, Appendix C.

Suitable for use as a staircase ventilator or roof mounted lobby/ corridor ventilator and to provide external roof access.

Description

A combined AOV smoke ventilator and roof access hatch designed providing either 1.0 or 1.5 m² measured free area in accordance with Approved Document B, Appendix C.

It is suitable for use as a staircase ventilator or roof mounted lobby/ corridor ventilator and to provide external roof access.


Features and benefits:

  • A wide range of applications: installed onto roofs providing high level smoke control extract as well as roof access. Its polycarbonate flap option allows the entry of natural daylight.
  • Weather resistant: The sealing system consists either of EPDM profiles which keep air leakage down to a minimum.
  • Durable: The AXS 140 flap is manufactured from tough, corrosion resistant aluminium with aluminium hinges and stainless steel pivots. It is manufactured under the ISO 9001 quality standard.
  • Large opening angle: Opens to 140⁰ which permits it to meet the requirements of EN 12101-2 for this kind of product.
  • Certified performance: Exhaustively tested and certified to EN 12101-2: 2003 in accredited third party test laboratories and is CE marked.
  • Manufactured under the ISO 9001 quality and ISO 14001 environmental management standards.
  • High thermal performance: Thermal performance varies with size and options, ranging from 1.3 to 2.4 W/m²K.
  • High acoustic performance: A sound reduction of up to 29 dB Rw may be achieved.
  • Low silhouette: No ugly and inconvenient wind deflectors are needed.

General information

Color

Silver

Guidance for specification option:

Standard (mill finish).

Other

Guidance for specification option:

RAL colour.

Finish

Mill finish

Powder-coated

Guidance for specification option:

Polyester powder-coated.

Material

Aluminium

Stainless steel

EPDM

Shape

Rectangle

Length

1350 mm

1600 mm

Width

1600 mm

1850 mm

Height

398 mm

Uniclass

Pr_70_65_04_56 Natural smoke and heat exhaust ventilatorsPrimary

CAWS

L10/45 Rooflights

L10/460 Rooflights

L10/47 Roof ventilators

L10/490 Roof ventilators

Product range

Natural flap ventilators

Specification data - Natural smoke and heat exhaust ventilators

Opening type

B.

Mounting

Roof-mounted.

Aerodynamic free area

1.0 m².

Reliability classification

Re 50.

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.


Watertightness: Rain defence tested to 75 m/h (at 13 m/s).

Sound insulation: <29 dB Rw.

Snow load classification

250 N/m².

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.

Low ambient temperature classification

T (-05).

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.

Wind load classification

WL 1500.

Guidance for specification option:

1500 N/m².

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.


Air permeability (to BS EN 12207): Class 4.

Resistance to heat classification

B300.

Guidance for specification option:

Resistance to fire (to BS EN 13501-1): E.

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.

Arrangement

Insulated aluminium panel.

Polycarbonate panel.

Dimensions

-

Length

1600 mm.

Guidance for specification option:

Overall length.

Width

1350 mm.

Guidance for specification option:

Overall width.

Height

398 mm.

Controls

24 V d.c. linear actuator (drive in/ drive out).

Guidance for specification option:

Motor: 2.6 A; 62.4 W; 1550 N.

Manufacturer guidance

Mounted on a pivoting carriage capable of opening the lid to the fire position of 140° from the horizontal within 60 seconds and of re-closing it.

Materials

-

Ventilator

-

Frame

Aluminium.

Guidance for specification option:

Thermally broken aluminium frame with continuous seals for excellent airtightness. Opens to 140° from the horizontal.

Glazing

As arrangement.

Finish

Mill finish.

Polyester powder-coated.

Guidance for specification option:

Insert colour requirements below.

Standard 40 µm.

Colour

Silver.

Guidance for specification option:

Standard for mill finish.

RAL.

Guidance for specification option:

Many colour options available; consult manufacturer for details and insert requirements.

Integral upstands

-

Material

Manufacturer's standard.

Guidance for specification option:

Thermally broken, 40 mm-thick welded insulated and thermally broken aluminium. EN AW-6063 T6 (extrusion) and EN AW-3005 H14 (sheet) aluminium alloy.

Finish

As ventilator.

Mill finish.

Polyester powder-coated.

Guidance for specification option:

Insert colour requirements below.

Standard 40 µm.

Colour

As ventilator.

Silver.

Guidance for specification option:

Standard for mill finish.

RAL.

Guidance for specification option:

Many colour options available; consult manufacturer for details and insert requirements.

Seals

EPDM profiles.

Guidance for specification option:

Keeps air leakage down to a minimum.

U-value

Up to 1.3 W/m²K.

Fixing

Fixing flange for curb.

Guidance for specification option:

Installation angle must be at 0° (horizontal).