Aspirating Smoke Detector - VESDA Laser Industrial (VLI) - Aspirating Smoke Detector

Verified by manufacturer 2 days ago

VLI-880

XTRALIS Variant:

Aspirating smoke detector providing very early warning for industrial applications and harsh environments.

Jump to:
+44 (0) 203 409 1779 Website

Application

Suitable for a range of application areas, for example:

  • Mines.
  • Manufacturing and processing plants.
  • Conveyors.
  • Petrochemical plants.
  • Tunnels.
  • Grain silos.
  • Power generation facilities.
  • Timber, pulp and paper plants.
  • Warehouses.
  • Water treatment plants.
  • Transportation hubs.
  • Fertilizer plants.
  • Abattoirs.
  • Laundries.
  • Cold stores.
  • Equipment and machinery.
  • Textile plants.
  • Elevator shafts
  • Equestrian centers.
  • Livestock/ animal facilities.

Description

Aspirating smoke detector providing very early warning for industrial applications and harsh environments.

This configuration protects environments of up to 2000 m².

The VLI detector combines a fail-safe intelligent filter with an advanced clean-air barrier for optics protection, allowing the use of absolute detection and a long detection chamber life without the need for re-calibration.

Features and benefits:

  • Suitable for Class 1 Division 2 applications - Groups A, B, C and D.
  • Up to 2,000 m² coverage.
  • Up to four inlet pipes.
  • Total pipe length up to 360 m.
  • Five high intensity status light emitting diodes (LEDs) for greater visibility.
  • Robust absolute smoke detection.
  • Intelligent filter.
  • Lint trap to capture fibrous particulates.
  • Sub-sampling probe (inertial separator).
  • Secondary filter.
  • Clean air barrier for optics protection.
  • Referencing.
  • AutoLearn™ Smoke and Flow.
  • Clean Air Zero™.
  • Air-path monitoring.
  • Five relays (Fire, Fault and 3 configurable).
  • Relays configurable as latching or non-latching.
  • Expandable GPI and relays.
  • Ultrasonic flow sensing.
  • Xtralis VSC, Xtralis VSM4 and ASPIRE software support.
  • IP66 enclosure.
  • Easy mounting with steel support bracket.
  • Modular field replaceable parts for ease of servicing.
  • Local USB configuration port.
  • Easy cable termination access.
  • Imperial and metric pipe ports.
  • Rubberized finish to external housing.
  • CE/ UKCA Certified.

General information

Color

Black

Material

Rubber

Shape

Rectangle

Length

180 mm

Manufacturer guidance

Depth.

Width

426.5 mm

Height

316.5 mm

Uniclass

Pr_75_80_30_03 Aspirating smoke detectorsPrimary

CAWS

W90/328 Point smoke detectors

SKU Code

VLI-880

Specification data - Aspirating smoke detectors

Classification data

Standard

To BS EN 54-20.

Third-party certification

LPCB, FM, ActivFire, NF, SIL 2 (as per IEC 61508)-approved.

Sensitivity class

To BS EN 54-20, Class A.

Guidance for specification option:

24 holes / Alert = 0.06% obs/m.

To BS EN 54-20, Class B.

Guidance for specification option:

28 holes / Fire-1 = 0.15% obs/m.

To BS EN 54-20, Class C.

Guidance for specification option:

60 holes / Fire-1 = 0.15% obs/m.

Sampling pipe

-

Arrangement

-

Manufacturer guidance

  • Up to four inlet pipes possible.
  • Minimum airflow per pipe: 20 l/m.
  • Internal diameter 15–21 mm. External diameter 25 mm.

Consult manufacturer and insert requirements.

Length (maximum)

360 m.

Air inlet holes (maximum)

24.

Guidance for specification option:

For Class A.

28.

Guidance for specification option:

For Class B.

60.

Guidance for specification option:

For Class C.

Coverage (minimum)

2000 m².

Enclosure

-

Material

Rubber.

Ingress protection (minimum)

IP 66.

Power supply

24 V d.c.

Controls

-

Display type

Light-emitting diode display (LED).

Functions

Four alarm thresholds (two pre-alarms and two alarms).
On board memory capable of recording 18 000 events.

Guidance for specification option:

Event log: Up to 18 000 events stored in FIFO format, time and date stamped in separate, non-volatile, logs.

Smoke level, user actions, alarms and faults with time and date stamp.

AutoLearn™: Minimum 15 minutes, Maximum 15 days. Recommended minimum 14 days.

Display the following information

Alert, Action, Fire 1 and Fire 2.
Disabled.
Fault.
Power.

Guidance for specification option:

Threshold setting range:

  • Alert: 0.05 to 1.990% obs/m.
  • Action: 0.1 to 1.995% obs/m.
  • Fire1: 0.15 to 2.0% obs/m.
  • Fire2: 0.155 to 20.0% obs/m.

Relay contacts

5 no. 2 A/ 30 V d.c relays.

Guidance for specification option:

Fire (NO), Fault (NC), Configurable (NO) - configurable as latching or non-latching.

Weight

6.035 kg.

Power consumption

Nominal: 10 W; In alarm: 10.5 W.

Operating temperature

Ambient: 0–38°C.
Sampled air: -20 to +60°C.

Operating humidity

5–95% RH, non-condensing.

SoftwareVersion

Xtralis VSC/ ASPIRE/ VSM4.

Sensitivity

0.05 to 20% obs/m.

Cable

4 x 25 mm cable entries.

Guidance for specification option:

Cable terminations: Screw terminal blocks.

Communications

N/A.

Accessories

Not required.
Power supply unit - VPS-220-E5.

Guidance for specification option:

This is the original unit within the range. Internally is an EN 54-4 certified Power Supply rated to provide a 0.5 A continuous 24 V d.c. supply while also charging the batteries (not supplied) which can be a 7, 12 or uniquely, 14 Ah arrangement. As such the unit can be used with confidence to power, and provide 24 hr standby (plus 0.5 hr in alarm), for the VESDA detectors.

Power supply unit - VPS-215-E5.

Guidance for specification option:

This is the budget unit within the range. It is intended as a low-cost unit to supply a single pipe ASD detector which only requires 7 Ah batteries such as the VESDA VLF-250. A simple but elegant construction and no LEDs on the lid keep the cost of the unit to a minimum. The unit can also be inverted where necessary by rotating the lid. The internal charger is EN 54-4 certified and internal LEDs are provided to indicate OK (output healthy) and Fault.

Power supply unit - VPS-250-E5.

Guidance for specification option:

This power supply is capable of powering larger ASD units. It may also be used for installations with multiple detectors and/ or remote displays. The internal charger is EN 54-4 certified to power loads up to 3 A with space and charging capacity for batteries up to 38 Ah. Uniquely, the unit is supplied with the provision to deliver 4 separately fused outputs – recommended when it is used to power multiple detectors or disparate loads.

VLI Intelligent Filter - VSP-030.
VLI Secondary Foam Filter - VSP-031.
Xtralis In-Line Filter.
VLI Aspirator - VSP-032.
VLI Chamber Assembly - VSP-033.
ASD Sampling Hole Clips.
Refrigerated Storage Sampling Kit - VSP-860.
Tamper Proof Sampling Point.
Flush Mount Sampling Point.
Automatic Purging Unit - F-BO-AFE70.
VESDA High Level Interface (HLI).
VESDA Remote Display Module.
VESDA 19" Sub Rack.
VESDA LCD Programmer.
Xtralis Test Transformer.
Smoke Pen.

Sustainability data

Material

Rubber

Similar products from XTRALIS

Addressable Aspirating Smoke Detector - VESDA-E VEA - Aspirating Smoke Detector

Addressable Aspirating Smoke Detector - VESDA-E VEA - Aspirating Smoke Detector

Aspirating Smoke Detection - VESDA-E VES - Aspirating Smoke Detector

Aspirating Smoke Detection - VESDA-E VES - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA LaserFocus (VLF) - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA LaserFocus (VLF) - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA-E VEP - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA-E VEP - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA-E VEU - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA-E VEU - Aspirating Smoke Detector

FAAST FLEX™ - Aspirating Smoke Detector - Aspirating Smoke Detector

FAAST FLEX™ - Aspirating Smoke Detector - Aspirating Smoke Detector