NBS Source
I'm a manufacturer
Compare variants

Aspirating Smoke Detector - VESDA-E VEP - Aspirating Smoke Detector

Verified by manufacturer 2 days ago

VEP-A00-1P (with LEDs) - 1 pipe

XTRALIS Variant:

Aspirating smoke detector providing early warning and alarm.

Jump to:
+44 (0) 203 409 1779 Website

Application

Suitable for a range of application areas, for example:

  • Accommodation (apartments, hotels, shops and offices).
  • Correctional facilities.
  • Clean rooms.
  • Cold storage.
  • Cultural/ heritage.
  • Data and telecom.
  • Education.
  • Hospitals and healthcare.
  • Insurance.
  • Marine.
  • Nuclear facilities.
  • Offices.
  • Oil and gas.
  • Portable switch rooms.
  • Power generation.
  • Records storage.
  • Retail.
  • Transportation.
  • Wind power generation.
  • Warehousing.

Description

Aspirating smoke detector providing early warning and alarm.

This configuration has advanced detection technology to provide very early warning and the best nuisance alarm rejection to a wide range of applications. Built on the flair detection technology and years of application experience, VEP detectors achieve consistent performance over their lifetime via absolute calibration. In addition, the VEP delivers a range of revolutionary features that provide user value.

Features and benefits:

  • Suitable for Class 1 Division 2 applications - Groups A, B, C and D.
  • One and four pipe models for different applications.
  • Flair detection technology delivers reliable very early warning in a wide range of environments with minimal nuisance alarms.
  • Sensitivity Range - 0.005 to 20% obs/m
  • Short wavelength laser-based detection: High sensitivity from small particle light scattering, no drift compensation required since focused light directed at target gives low backgrounds, high stability with temperature and time.
  • Multi-stage filtration and optical protection with clean air barriers ensures lifetime detection performance.
  • Four alarm levels and a wide sensitivity range deliver optimum protection for the widest range of applications.
  • Intuitive liquid crystal display (LCD) icon display provides instant status information for immediate response.
  • Flow fault thresholds per port accommodate varying airflow conditions.
  • Smart on-board filter retains dust count and remaining filter life for predictable maintenance.
  • Extensive event log (20 000 events) for event analysis and system diagnostics.
  • AutoLearn™ smoke and flow for reliable and rapid commissioning.
  • Referencing to accommodate external environmental conditions to minimise nuisance alarms.
  • Backward compatible with VLP and VESDAnet.
  • Ethernet for connectivity with Xtralis software for configuration, secondary monitoring and maintenance.
  • USB for PC configuration, and firmware upgrade using a memory stick.
  • Two programmable GPIs (one monitored) for flexible remote control.
  • Field replaceable sub-assemblies enable faster service and maximum uptime.
  • CE/ UKCA marked.

General information

Color

Black

Material

Plastic

Shape

Rectangle

Length

135 mm

Manufacturer guidance

Depth.

Width

350 mm

Height

225 mm

Uniclass

Pr_75_80_30_03 Aspirating smoke detectorsPrimary

CAWS

W90/328 Point smoke detectors

SKU Code

VEP-A00-1P

Specification data - Aspirating smoke detectors

Classification data

Standard

To BS EN 54-20.

Guidance for specification option:

& ISO 7240-20.

Third-party certification

CSFM, FM, ActivFire, VdS, NF-SSI, and CCC-approved.

Sensitivity class

To BS EN 54-20, Class A.

Guidance for specification option:

Four pipe:

40 holes / Fire 1 = 0.028% obs/m.

To BS EN 54-20, Class B.

Guidance for specification option:

Four pipe:

80 holes / Fire 1 = 0.027% obs/m.

To BS EN 54-20, Class C.

Guidance for specification option:

Four pipe:

100 holes / Fire 1 = 0.056% obs/m.

Sampling pipe

-

Arrangement

Single-pipe.

Guidance for specification option:

1 pipe. 100 m.

Manufacturer guidance

  • Minimum airflow per pipe: 15 l/m.
  • Inlet: External diameter 25 mm. Exhaust: External diameter 25 mm.

Length (maximum)

130 m.

Air inlet holes (maximum)

30.

Guidance for specification option:

For Class A.

40.

Guidance for specification option:

For Class B.

45.

Guidance for specification option:

For Class C.

Coverage (minimum)

1000 m².

Enclosure

-

Material

Plastic.

Ingress protection (minimum)

IP 40.

Power supply

24 V d.c.

Controls

-

Display type

Light-emitting diode display (LED).

Functions

Four alarm thresholds (two pre-alarms and two alarms).
On board memory capable of recording 20 000 events.

Guidance for specification option:

Event log: Up to 20 000 events.

Smoke level, user actions, alarms and faults with time and date stamp.

AutoLearn: Detector learns Alarm Thresholds and Flow Fault thresholds by monitoring the environment.

Display the following information

Alert, Action, Fire 1 and Fire 2.
Disabled.
Fault.
Power.

Guidance for specification option:

Threshold setting range:

  • Alert: 0.005% to 2.0% obs/m.
  • Action: 0.005% to 2.0% obs/m.
  • Fire1: 0.010% to 2.0% obs/m.
  • Fire2: 0.020% to 20.0% obs/m.

Relay contacts

7 no. 2 A/ 30 V d.c. programmable relays.

Guidance for specification option:

Configurable as latching or non-latching.

Weight

4.4 kg.

Power consumption

Aspirator setting fixed: Quiescent: 8.8 W; In alarm: 9.6 W.

Operating temperature

Ambient: 0–38°C.
Sampled air: -20 to +60°C.

Operating humidity

5–95% RH, non-condensing.

SoftwareVersion

Xtralis VSC/ ASPIRE.

Sensitivity

0.005 to 20% obs/m.

Cable

4 x 26 mm cable entries.

Guidance for specification option:

Cable terminations: Screw terminal blocks.

Communications

VESDAnet.

Accessories

Not required.
Power supply unit - VPS-250-STX5-SLV.

Guidance for specification option:

These are the deeper units designed for installation with a VESDA-E detector (at all fan speeds). The internal charger is EN 54-4 certified and is rated to provide a 3 A continuous 24 V d.c. supply. There is space for up to 24 Ah

batteries (not provided). The unit also provides a non-certified setting which enables it to power loads up to 3.4 A

while recharging batteries up to 24 Ah in accordance with EN 54-4.

Power supply unit - VPS-250-STX5.

Guidance for specification option:

These are the deeper units designed for installation with a VESDA-E detector (at all fan speeds). The internal charger is EN 54-4 certified and is rated to provide a 3 A continuous 24 V d.c. supply. There is space for up to 24 Ah

batteries (not provided). The unit also provides a non-certified setting which enables it to power loads up to 3.4 A

while recharging batteries up to 24 Ah in accordance with EN 54-4.

Power supply unit - VPS-220-STX5-SLV.

Guidance for specification option:

These are the shallower units in the range with depth and width matching the VESDA-E detectors. Internally, they provide an EN 54-4 certified Power Supply rated to provide a 0.5 A continuous 24 V d.c. supply whilst also charging the batteries (not supplied) which can be a 7, 12 or uniquely, 14 Ah arrangement. As such the unit can be used with confidence to power, and provide 24 hr standby (plus 0.5 hr in alarm), for the VESDA VLF-500, VESDA-E VEP & VESDA-E VES detectors and also the VESDA-E VEU detectors up to fan speed 5. The unit also provides a non-certified setting which enables it to power loads up to 1A while recharging batteries up to 12 Ah in accordance with EN 54-4.

Power supply unit - VPS-220-STX5.

Guidance for specification option:

These are the shallower units in the range with depth and width matching the VESDA-E detectors. Internally, they provide an EN 54-4 certified Power Supply rated to provide a 0.5 A continuous 24 V d.c. supply whilst also charging the batteries (not supplied) which can be a 7, 12 or uniquely, 14 Ah arrangement. As such the unit can be used with confidence to power, and provide 24 hr standby (plus 0.5 hr in alarm), for the VESDA VLF-500, VESDA-E VEP & VESDA-E VES detectors and also the VESDA-E VEU detectors up to fan speed 5. The unit also provides a non-certified setting which enables it to power loads up to 1A while recharging batteries up to 12 Ah in accordance with EN 54-4.

ASD Sampling Hole Clips.
Refrigerated Storage Sampling Kit - VSP-860.
Tamper Proof Sampling Point.
Flush Mount Sampling Point.
Filter Cartridge - VSP-005.
Xtralis In-Line Filter.
Automatic Purging Unit - F-BO-AFE70.
VESDA High Level Interface (HLI).
VESDA Remote Display Module.
VESDA 19" Sub Rack.
VESDA LCD Programmer.
Xtralis Test Transformer.
Smoke Pen.

Manufacturer guidance

Spare parts are also available - consult manufacturer for details.

Sustainability data

Material

Plastic

Similar products from XTRALIS

Addressable Aspirating Smoke Detector - VESDA-E VEA - Aspirating Smoke Detector

Addressable Aspirating Smoke Detector - VESDA-E VEA - Aspirating Smoke Detector

Aspirating Smoke Detection - VESDA-E VES - Aspirating Smoke Detector

Aspirating Smoke Detection - VESDA-E VES - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA Laser Industrial (VLI) - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA Laser Industrial (VLI) - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA LaserFocus (VLF) - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA LaserFocus (VLF) - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA-E VEU - Aspirating Smoke Detector

Aspirating Smoke Detector - VESDA-E VEU - Aspirating Smoke Detector

FAAST FLEX™ - Aspirating Smoke Detector - Aspirating Smoke Detector

FAAST FLEX™ - Aspirating Smoke Detector - Aspirating Smoke Detector