Verified by manufacturer 4 months ago
1050 x 1050 mm with 365 mm PVC Kerb
UK Conformity Assessed (UKCA)
Certificate type
AOV smoke vent comprising PVC kerb with a polycarbonate dome. Automatic opening vents are for flat and low pitch roofs. Manufactured by Brett Martin, part of the Mardome rooflight range.
AOV smoke vents are designed to automatically extract smoke in the event of a fire. Typically sited on flat roofs above corridors and stairwells, the vents open to an angle of 140 degrees in less than 60 seconds. The range is fully tested and certified in accordance with BS EN 12101-2. Covering standards for safety, security, non-fragility and fire safety with the full guarantee of an established, accredited UK manufacturer. Fully certified to approved document B.
Features and benefits:
Certification and regulatory information:
Operation and options:
Control panel:
Color | White |
Finish | Gloss |
Material | Polycarbonate PVC-U Steel |
Shape | Square Rectangle |
Length | 1050 mm 1200 mm 1350 mm 1500 mm 1650 mm |
Width | 1050 mm 1200 mm 1350 mm 1500 mm 1650 mm |
Warranty description | Ten year |
Uniclass | |
CAWS | L10/45 Rooflights L10/460 Rooflights L10/47 Roof ventilators L10/490 Roof ventilators |
Standard | To BS EN 12101-2. |
Third-party certification | CE marked. |
Mounting | Roof-mounted. |
Aerodynamic free area | 0.49 m² (without wind deflector); 0.68 m² (with wind deflector).Guidance for specification option: 0.44 Cv (without wind deflector); 0.62 Cv (with wind deflector). |
Reliability classification | Re 1000. |
Snow load classification | SL 500. |
Low ambient temperature classification | T (-15). |
Wind load classification | WL 1500. |
Resistance to heat classification | B300 30. |
Arrangement | Roof hatch. |
Dimensions | |
Length | 1050 mm. |
Width | 1050 mm. |
Height | 365 mm. |
Controls | Control system.Guidance for specification option: It is recommended that Mardome Smoke Vents are connected to the Smoke Vent control panel available from Access Building Products Ltd. The control panel is designed to be used with the actuator of the Mardome Smoke Vent and provides a battery backup and additional line monitoring functionality. A Mardome Smoke Vent can be installed alongside other EN 12101-10 compliant control systems but Access Building Products Ltd cannot provide technical support concerning the control of the product and do not keep a list of compatible control systems. Installing with an alternative EN12101-10 control system will not affect the guarantee of the product. |
Initiation | Guidance for specification option: Control panel can be activated from: Manual override switches, by dedicated smoke detectors or through integration with existing smoke detection and or fire alarm systems. |
Materials | |
Ventilator | |
Frame | PVC-U. |
Glazing | Polycarbonate.Guidance for specification option: The outer dome of Mardome Smoke Vent is manufactured from 3 mm impact resistant Marlon FSX Longlife polycarbonate sheet which is co-extruded with a UV protective coating to both sides. The inner domes are manufactured from 2 mm impact resistant Marlon FSX Longlife polycarbonate sheeting for double and triple skin options. |
Finish | Gloss. |
Colour | White. |
Integral upstands | |
Material | PVC-U. |
Finish | Gloss. |
Colour | White. |
Accessories | Not required.Control panel system.Guidance for specification option: The EN12101-10:2005 approved and certified Mardome Smoke Vent Control Panel System is available in 5A and 8A options and comes with a built-in comfort switch at the front. See TB286 for more information. Fire switch.Guidance for specification option: The Mardome Fire Switch (IP40) is developed to be used together with the Mardome Smoke Vent Control Panel System. Its function is to open the Smoke Vent and activate the alarm. It comes with a breakable glass and is available in orange colour as standard. Fireman's priority switch.Guidance for specification option: The Mardome Fireman’s Priority Switch (IP40) is developed to be used together with the Mardome Smoke Vent Control Panel System. Its function is to open/close the Smoke Vent without influencing the alarm situation. It comes with a breakable glass. Smoke dector.Guidance for specification option: The Mardome Smoke Detector allows early fire detection with a visual ‘release’ display. It is available in white as standard. Wind deflectors.Guidance for specification option: Wind deflectors manipulate the air flow over and around the AOV, helping increase the aerodynamic free area (AA) of the AOV. In all cases the wind deflectors increase the Aerodynamic Free Area, meaning a smaller AOV with wind deflectors can match or out perform a bigger AOV without. This is particularly useful when needing to achieve an Aerodynamic Free Area of more than 0.70 Aa m2 in a stairwell as per the requirement of EN 12101-2. |
Free area | 0.72 m². |
Clear opening | 900 x 900 mm. Guidance for specification option: Roof opening area: 1.10 m². Manufacturer guidanceDaylight free area size. |
Kerb | 365 mm PVC Kerb. |
U-value | 1.6—2.1 W/(m²·K) (double skin); 1.2—1.5 W/(m²·K) (triple skin). |
Sound absorption | 20 dB (double skin); 22 dB (triple skin). |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Recyclability | Recyclable Guidance for specification option: The polycarbonate, PVC-U, steel and aluminium which comprise the product can be recycled at the end of useful product life. |
Platform | Compatible | Version |
---|---|---|
- | 1 |