Verified by manufacturer 2 months ago
ATV630U07N4
Variable speed drive.
Motor control applications across machines, processes, and buildings.
Variable speed drive that delivers a high performance in motor control applications across machines, processes, and buildings. With built-in intelligence, these devices gather and share data to improve operational efficiency, safety, and reliability.
Features and benefits:
Standards/ certifications:
Color | Black |
Shape | Rectangle |
Length | 203 mm |
Width | 144 mm |
Height | 350 mm |
Warranty description | 18 months |
Uniclass | |
CAWS | V90/430 Electrical accessories |
SKU Code | ATV630U07N4, ATV630U15N4, ATV630U22N4, ATV630U30N4, ATV630U40N4, ATV630U55N4, ATV630U75N4, ATV630D11N4, ATV630D15N4 |
Standards | BS EN IEC 61800-3. |
Rated operational voltage (Ue) | 380–480 V a.c. |
Rated operational current (In) | 1.5 A at 380 V (normal duty). 1.3 A at 480 V (normal duty). 0.9 A at 380 V (heavy duty). 0.8 A at 480 V (heavy duty). |
Rated power (kW) | 0.75 kW. |
Rated operational frequency | 50–60 Hz. |
Output | |
Frequency range | 500 kHz (maximum). |
Controls | |
Display type | LCD (0.1 Hz). |
User interface | Ethernet (2-wire RS 485). |
Drive protection | Thermal protection. Safe torque off (STO). Overheating. Overcurrent between output phases and earth. Overload of output voltage. Short-circuit protection. Motor phase break. Overvoltage's on the DC bus. Line supply overvoltage. Line supply undervoltage. Line supply phase loss. Overspeed. Break on the control unit. |
Motor protection | Thermal protection. Safe torque off (STO). Motor phase break. |
Relay type | R1A, R1B, R1C 250 V AC 3000 mA. R1A, R1B, R1C 30 V DC 3000 mA. R2A, R2C 250 V AC 5000 mA. R2A, R2C 30 V DC 5000 mA. R3A, R3C 250 V AC 5000 mA. R3A, R3C 30 V DC 5000 mA. |
Communications protocol | Modbus TCP. Ethernet. Modbus serial. |
Enclosure | |
Mounting arrangement | Surface. |
Colour | Black. |
Ingress protection (minimum) | IP21. |
Accessories | Not required. Passive filter. Guidance for specification option: Improves an installations power quality by reducing the harmonics levels, while keeping existing drives installed. |
LED lighting | 3 LEDs for local diagnostics. |
Net weight | 4.5 kg. |
Noise | 54.5 dB (conforming to 86/188/EEC). |
Operating temperature | -15 to 50°C (without derating). |
Power | 0.75 kW (normal duty). |
RelativeHumidity | 5–95% without condensation (conforming to IEC 60068-2-3). |
Slots | Slot A: communication module, Profibus DP V1. Manufacturer guidanceOption card. |
Recyclability | Up to 85% |