NBS Source
I'm a manufacturer
Compare variants

Acti9 Outgoing Devices – Miniature Circuit Breakers (1 pole)

Verified by manufacturer 9 days ago

ACTI9 IC60H 1P 1A B MCB

Schneider Electric Ltd Variant:

iC60 circuit breakers ensure the protection of the electrical installation against overloads and short-circuits.

Jump to:
+44 (0)870 608 8608 Website

Application

Multi-standard circuit breakers which protect against short-circuit and overload currents.

Description

iC60 circuit breakers ensure the protection of the electrical installation against overloads and short-circuits.


Features and benefits:

  • Insulated terminals, IP20.
  • Visi-trip window: Fault tripping is indicated by a red mechanical indicator on the front face.
  • Positive contact indication: Suitable for industrial isolation according to IEC/EN 60947-2 standard. The presence of the green strip indicates physical opening of the contacts and allows operations to be performed on the downstream circuit with complete protection.
  • Large circuit labelling area.


Increased product service life thanks to:

  • Overvoltage resistance by high level of industrial performances conception (pollution degree, rated impulse withstand voltage and insulation voltage).
  • High performance limitation (see limitation curves).
  • Fast closing independent of the speed of actuation of the toggle.
  • Remote indication, open/ closed/ tripped, by optional auxiliary contacts.
  • Top or bottom electrical feeding.

General information

Color

White

Material

Plastic

Guidance for specification option:

Approx. 43%.

Metal

Guidance for specification option:

Approx. 52%.

Other

Guidance for specification option:

Approx. <5%.

Shape

Rectangle

Length

78.5 mm

Width

18 mm

Height

85 mm

Uniclass

Pr_65_72_27_52 Miniature circuit breakersPrimary

CAWS

V90/320 Distribution boards

V90/319 Cable distribution cabinets

V90/320 Distribution boards

V90/320 Distribution boards

V90/110 Low-voltage supply

V90/319 Cable distribution cabinets

Product range

Acti 9

Specification data - Miniature circuit breakers

Standards

To IEC/EN 60947-2 and IEC/EN 60898-1.

Rated current (InA)

1 A.

Rated operational voltage (Ue)

Manufacturer's standard.

Guidance for specification option:

Details may vary based on Type specified; consult manufacturer's literature for details and insert if required.

Rated impulse withstand voltage (Uimp)

6 kV.

Guidance for specification option:

Details may vary based on Type specified; consult manufacturer's literature for details and insert if required.

Rated frequency

Manufacturer's standard.

Guidance for specification option:

Details may vary based on Type specified; consult manufacturer's literature for details and insert if required.

Number of poles

One.

Rated short-circuit capacity (Icn)

Manufacturer's standard.

Guidance for specification option:

Details may vary based on Type specified; consult manufacturer's literature for details and insert if required.

Tripping characteristic

See variant type.

Mounting method

DIN rail.

Guidance for specification option:

35 mm.

Accessories

Guidance for specification option:

Consult manufacturer's literature for options and insert requirements, or omit.

Sustainability data

Recyclability

51%

Guidance for specification option:

Potential recyclability. Based on “ECO’DEEE recyclability and recoverability calculation method” (version V1, 20 Sep. 2008 presented to the French Agency for Environment and Energy Management: ADEME).

Similar products from Schneider Electric Ltd

Acti9 Outgoing Devices – Miniature Circuit Breakers (2 pole)

Acti9 Outgoing Devices – Miniature Circuit Breakers (3 pole)

Acti9 Outgoing Devices – Miniature Circuit Breakers (4 pole)

Acti9 Outgoing Devices – VIGI - Earth Leakage Protection