Acti9 Outgoing Devices – Arc Fault Detection

Verified by manufacturer 4 months ago

iARC 1P+N 32A AFDD

Schneider Electric Ltd Variant:

Acti9 active arc fault detection device.

Jump to:
+44 (0)870 608 8608 Website

Application

Examples of where AFDDs can be used include:

  • in locations with sleeping accommodations (e.g. hotels, nursing homes, bedrooms in homes),
  • in locations with risks of fire due to high quantities of flammable materials (e.g. barns, wood-working shops, stores of combustible materials),
  • in locations with combustible constructional materials (e.g. wooden buildings),
  • in fire propagating structures (e.g. high rise buildings),
  • in locations where irreplaceable goods are housed (e.g. museums).


The installation of Acti9 Active is highly recommended by the manufacturer to protect circuits with highest risk of fire, such as:

  • protruding cables (risk of knocks),
  • outside cables (greater risk of deterioration) ,
  • unprotected cables in secluded areas (like storage rooms) ,
  • ageing, deteriorating wiring or wiring for which the connection boxes are inaccessible.


The product must not be installed on circuits requiring a high level of continuity of service. Not compatible with ATEX regulations.

Description

Acti9 Active is an arc fault detection device with overload, short circuit and residual current protection, which aims to reduce the risk of electrical fire.


By continuously analyzing a large number of electrical parameters, it detects the appearance of electric arcs that are responsible for starting fires. It isolates the circuit concerned which reduces flame appearance occurrence.


Regulation 421.1.7 of BS 7671: 2018 (IET Wiring Regulations 18th Edition) recommends the use of AFDD to protect against arc fault in AC final circuits.


A-SI type:

The A-SI type provides increased immunity from electrical interference and polluted or corrosive environments.


Wireless-communication device:

  • Used together with a concentrator or a gateway to collect and process the data, Acti9 Active AFDD provides circuit monitoring and diagnosis down to load level.
  • Wireless-communication technology simplifies switchboard wiring and commissioning operations: no wiring is required for the Acti9 Active AFDD to communicate with the concentrator or the gateway.


Features and benefits:

  • Customizable thresholds for pre-alarms.
  • Overload.
  • Earth leakage.
  • Overvoltage.
  • Indication for nature of electrical fault.
  • Historical data.
  • Protection logs.
  • U, I & P measuring.
  • Load monitoring.
  • Protection for people, appliances, circuit, and against fire MCB+MSU+RCD+AFDD. 

General information

Color

White

Uniclass

Pr_65_72_27_04 Arc fault detection devices

Primary

CAWS

V91/320 Distribution boards

V91/315 Cable distribution cabinets

V90/320 Distribution boards

V90/319 Cable distribution cabinets

Product range

Acti 9

Specification data - Arc fault detection devices

Standards

To IEC/BS EN 62606, BS EN IEC 61009-2-1, BS EN IEC 60947-2
IEC/BS EN 60898-1.

Format

AFDD with overload, short circuit and residual current protection.

Rated operational voltage (Un)

230 V AC.

Rated current (InA)

32 A.

Rated frequency

50 Hz.

Number of poles

One + neutral.

Sustainability data

Embodied carbon

A1-A3 (production stage) as defined in BS EN 15804

6.92 kg CO₂ eq/unit

Recyclability

47%