Single vertical fire curtain barrier tested to BS EN 1634-1 and BS EN 1634-3.
Designed for multiple applications. Protected means of escape, atrium, lobbies, receptions, opening in walls, egress, corridor separation, boundary protection, escalators, stairs, lifts and lift lobbies. Regularly used in hospitals, schools, hotels, high buildings, mixed use, offices, military sites, retail, stadia, museums and galleries, prison and policing sector, industrial and utility applications, transport infrastructure and many others.
Fire and smoke curtain barrier.
Features and benefits:
Color | Other Guidance for specification option: Available in any RAL colour. |
Finish | Other Guidance for specification option: Standard C3 class with C3 high durability options. |
Material | Carbon steel Stainless steel |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Standards | To BS 8524-1, BS EN 1634-1, BS 476-6, -7, BS EN 12605, BS EN 14600, BS EN 13501-2 and BS EN 16034. |
Barrier assemblies | To BS 8524-1. |
Test standards | Vertical, horizontal and angled to BS EN 1634-1. |
Third-party certification | Warrington Fire Report 340986. |
Size | Manufacturer guidanceMaximum size (w x h): 10 000 x 6000 mm. (32 m²). Insert requirements. |
Performance | |
Smoke containment | No smoke seals. |
Fire resistance | 60 minutes.120 minutes. |
Accessories | Partial Drop.Guidance for specification option: The barrier shall have the facility to deploy to a pre-determined position to allow escape and initial smoke containment. The partial close position shall be site adjustable with an adjustable wait time in the partial close position of up to 10 minutes Emergency Retract.Guidance for specification option: The barrier can have an emergency retract interface for escape and emergency access. The interface shall be volt free, normally open (close on operation). The signal required shall be momentary with a site adjustable retract time. The emergency retract facility shall be operational as long as there is primary / secondary power available. BMS Interface.Guidance for specification option: The barrier has volt free c/o contacts to indicate whether the barrier is fully open or fully closed. Single Photo Cell.Guidance for specification option: Tested and Passed by Exova to BS 8524-1 Annex H Audio / Visual / Spoken Warning Unit.Guidance for specification option: The barrier has a volt free contact which indicates an active c/o (change over) contact which indicates an active alarm signal. An Audio / Visual / Spoken warning unit can be interfaced with this using power supplied by the primary / secondary source or via an external source. |
Radiation | 85 minutes <15 kW/m². |
Fabric | Fire curtains are formed from a fire rated fabric 0.54 mm thick stainless steel wire reinforced, with a specially formulated Aluminum pigmented and fire retardant polymer which provides a heat reflecting surface as well as other properties for smoke and fire. Guidance for specification option: The fabric has been independently tested for fire propagation in accordance with BS 476-6 in addition to this it also conforms to BS 476-7 which relates to surface spread of flame and in accordance with approved document B 2006. As a requirement of BS EN 1634-1, the fabric and curtain are tested as a complete assembly in compliance with BS EN 1363-1 and BS EN 1363-2. |
Barrel | Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards. |
Colour and finish | Manufacturer guidanceConsult manufacturer and insert requirements. Available in any RAL colour. |
Material | Carbon steel Stainless steel |