NBS Source
I'm a manufacturer

801F Flame Detector

Verified by manufacturer 2 months ago

ADT Fire and Security

Flame detector.

Jump to:
Website

Description

MXTechnology® addressable solar blind infrared flame detectors.


Standard or Intrinsically safe ATEX approved


MXTechnology® incorporates heat, optical, ionisation and

carbon monoxide detection. The flame

detector presents a cost effective solution to providing false alarm free flame detection for indoor applications.


Fully featured solar blind flame detector for indoor use and boast a high degree of false alarm immunity. The standard unit is the 801F and it is designed for direct connection to the MX digital loop, employing the same detector base or functional base as other800 series fire detectors.


The detector is designed to comply with EN/IEC 60079-0:2006, EN/IEC 60079- 11:2007 and EN/IEC 61241-11:2006 for intrinsically safe apparatus. Certified: ATEX code: Ex II 1 GD Ceneleccode: Ex ia IIC T4/Ex iaD 20 T135°C.


Features and benefits:

  • Solar Blind for false alarm free operation
  • Intrinsically safe or standard versions
  • Fast response to flame
  • Detect a 0.1 m² fire at a range of 20 m
  • Automatic health check feature
  • Discrete ultra low profile design
  • Fits a standard MX detector base or functional base
  • Integral alarm LED with 360 degree angle of view
  • Use T110 infrared test source (With separate adaptor)
  • Complies to EN 54-10 for Flame Detectors.

General information

Color

White

Other

Guidance for specification option:

Pantone colours.

Shape

Circle

Width

108 mm

Guidance for specification option:

Diameter

Height

21.2 mm

Uniclass

Pr_75_80_30_63 Point flame detectorsPrimary

CAWS

W90/327 Point heat detectors

Specification data - Point flame detectors

Standard

To EN 54-10, EN 50130-4, EN61000-6-3,EN/IEC 60079-0:, EN/IEC 60079-11 and EN/IEC 61241-11.

Third-party certification

Certified ATEX code: Ex II 1 GD Cenelec code: Ex ia IIC T4/Ex iaD 20 T135°C.

Mounting

Base-mounted.

Detector type

Infrared.

Operating range (minimum)

0.1 m² n-heptane at 20m (on axis).
0.4 m² n-heptane at 50m (on axis).

Guidance for specification option:

Field of View 100°.

Power source

From loop.

Manufacturer guidance

  • Loop Voltage: 20–40 V.
  • Quiescent current: 300 micro Amp typical.
  • Alarm current: 3 mA typical.


Operating temperature

-20 to +70°C.

RelativeHumidity

90% RH continuous (noncondensing) and up to 99% RH
intermittent (non-condensing).

Base

5” Universal Base.

5" I.S. Universal Base.

Colour:

White.

BIM objects

Platform Compatible Version
Revit
-

1

Literature

516.800.006 801F Flame Detector

516.800.006 801F Flame Detector