Cafco FENDOLITE® MII

Cafco FENDOLITE® MII

Promat UK Third party certifications:
  • Certifire Certificate

    Certifire Certificate

    Certificate type

Cement-based wet mix spray producing a monolithic coating able to withstand thermal shocks experienced typically in a high intensity hydrocarbon fire.

Jump to:
+44 (0)800 145 6033 www.promat.com

Application

Suitable for application by trowel in interior and fully exposed environments. Applied by plastering techniques enabling repairs to be completed without the need to introduce spray plant onto the site. Suitable substrates include: Existing Cafco FENDOLITE® MII, concrete, non-primed and primed steel. Concrete curing agents should not be used.

Description

Cement-based wet mix spray producing a monolithic coating able to withstand thermal shocks experienced typically in a high intensity hydrocarbon fire.

Concrete structures in particular will be protected from explosive spalling when protected using Cafco FENDOLITE® MII.

Although low in density, thus significantly reducing dead load, Cafco FENDOLITE® MII is highly durable and will not crack or spall under mechanical impact.

Used for application to construction elements such as concrete or individual steel sections


Features and benefits:

  • 30–240 minutes' fire resistance.
  • Part of a Promat steel protection system.
  • Protects structures from explosive spalling.
  • Highly durable and will not crack.
  • Durable solution, resistant to impact damage.
  • May be levelled to present a trowelled finish.
  • Can be easily removed and reinstated locally when additional fixings are required.

General information

Color

White

Off-white.

Material

Cement

Premix, based on vermiculite and Portland cement.

Uniclass 2015

Pr_35_31_68_43 Intumescent protective coatingsPrimary

CAWS

M22/120 Sprayed

Specification data - Intumescent protective coatings Enhanced data

Composition

Premix based on vermiculite and Portland cement.

Used with potable water added on site.

Colour

Off-white.

Strictly trowel finished only.

Product Reference

Cafco FENDOLITE® MII

Thickness

Practical thickness (minimum): 

8 mm when unreinforced, 15 mm when reinforced.

Insert requirement. The thickness of the fire protection for a given period of fire resistance in a cellulosic type fire relates to the A/V ratio of the section. For advice on thickness calculations for hollow sections, cellular beams, castellated sections, composite floors, upgrading of concrete slabs and more complex situations, contact manufacturer.

Coverage

100 m²/tonne.

Theoretical, at 15 mm thickness. Apply one or more coats as required.

Cure

By air drying.

Initial set:

2–6 hours.

At 20°C and 50% relative humidity.

Density

775 kg/m³ (±15%).

When dry and in place.

Combustibility

Euroclass A1.

To BS EN ISO 13501-1.

Smoke generation

Does not contribute to smoke generation.

ThermalConductivity

0.19 W/m·K.

At 20°C.

Specific heat

0.97 kJ/kg·K.

At 25–35°C.

Corrosion resistance

Does not promote corrosion of steel.

A primed substrate is recommended for long term corrosion resistance.

pH value

12.0–12.5.

Form

Wet mix spray.

(Formless).

Finish:

Trowel finished.

Environmental information

Contains Red List materials

No

Country of material origin

France

Country of product manufacture

France

Recyclability

Not recyclable

Third party certifications

  • CF 5172