Medipower™ Double Cabinet IPS - Medical IT Power Supply
Medipower™ Double Cabinet IPS - Medical IT Power Supply
Medipower™ Double Cabinet IPS - Medical IT Power Supply

Verified 10 days ago

Brandon Medical Co Ltd

Verified 10 days ago

Brandon Medical Co Ltd

Verified 10 days ago

Brandon Medical Co Ltd
Summary
Isolated power supply for group 2 medical locations.
Product certifications

Self-declared

Digital objects
-
-
Color
Grey
-
-
Finish
Powder-coated
-
-
Material
Steel
-
-
Shape
Rectangle
-
-
Length
350 mm
-
-
Width
550 mm
-
-
Height
1700 mm
-
-

Specification

Standards
-
-
-
Generally
In accordance with BS 7671, HD 60364-7-710, and HTM 06-01.
-
-
Safety
To BS EN 60601-1 and BS EN 61558-2-15.
-
-
Monitoring
To BS EN IEC 61557-1, BS EN 61557-8 and BS EN 61557-9.
-
-
Service conditions
-
-
-
Treatment locations
Suitable for medical group 2.
-
-
Clinical risk
To HTM 06-01, category 5 areas.
-
-
Configuration
-
-
-
Isolating transformer
4 kV·A.
-
-
Distribution
-
-
-
Number of ways
Available in functional blocks of 6, up to a maximum of 96.
-
-
Surge protection
Not required., Required.
-
-
Automatic transfer
From primary to secondary within 0.5 s.
-
-
Provision for maintenance
Not required., Break before make bypass switch.
-
-
Communications
CANbus (Controller Area Network bus).
-
-
Integration with other systems
-
-
-
Secondary supply
Not required., Integrated uninterruptible power supply (UPS).
-
-
Enclosure
-
-
-
Arrangement
Modular.
-
-
Mounting type
Floor-mounted., Wall-mounted.
-
-
Material
Mild steel.
-
-
Finish
Powder-coated.
-
-
Colour
Light grey (RAL 7035).
-
-
Ingress protection (minimum)
IP41.
-
-
Ventilation arrangement
Two fans.
-
-
Ancillary products
Local alarm panels (LAP).
-
-

Additional properties

Configuration
Double cabinet (DIPS).
-
-
Components
Incoming isolator.
Control and monitoring device - ILT.
-
-
Dimensions
1700 x 550 x 350 mm.
-
-
Air flow
42 m³/hr per IPS channel.
-
-
Protective earth bars
100 A.
-
-
Circuit breakers
24.
-
-
Rated frequency
50–60 Hz.
-
-
Input voltage
230 V a.c.
-
-
Current rating
17.4 A.
-
-
Power dissipation
Heat power dissipation no-load: <36 W.
Heat power dissipation 100%-load: <138 W.
-
-
Efficiency
96%.
-
-
Weight
52 kg.
-
-
Supply
Typical MCB Supply (A): C32 or D25.
Typical MCCB Supply (A): AF63/ AT30.
-
-
Accessories
Not required., MCB tripped monitoring., Network gateway., MODbus interface., Primary side outgoing RCBO’s (Type – 2C,25).
-
-

Sustainability data

Country of product manufacture
United Kingdom
-
-
Material
Steel
-
-