ELCO Aerotop Evo Plus - Air Source Heat Pump
ELCO Aerotop Evo Plus - Air Source Heat Pump
ELCO Aerotop Evo Plus - Air Source Heat Pump

Verified 4 days ago

Ariston Group UK Ltd

Verified 4 days ago

Ariston Group UK Ltd

Verified 4 days ago

Ariston Group UK Ltd
Summary
Outdoor air source heat pump with inverter technology and R-32 refrigerant, offering heating, cooling, and domestic hot water production with high energy efficiency.
-
-
Application
  • Suitable for heating, cooling, and domestic hot water production in residential and commercial buildings.
  • Designed for outdoor installation
-
-
Description

Aerotop Evo Plus is an air cooled heat pump equipped with full DC inverter technology and R-32 refrigerant designed for outdoor installation. It is available from 24 kW up to 94 kW in various versions. It offers energy efficiency with SCOP up to 4.54 (A+++ class) and SEER up to 4.81, with capacity modulation from 30% to 100%.

Features and benefits:

  • Management and production of domestic hot water up to 60°C.
  • Climate compensation with outdoor temperature.
  • Double set point adjustable.
  • Additional heating source management.
  • SG ready and EVU lock ready (remote on/ off).
  • Demand limit functionality.
  • Silent mode with speed reduction of compressors and fans.
  • Hydronic assembly with one inverter pump integrated.
  • Drain tray with electric heater made of steel AISI 316 for condensate collection and discharge.
  • Copper/ aluminum condenser coil with acrylic lining for resistance to airborne salt and moderate aggressive agents.
  • Anti-vibration mount support to reduce noise transmission.
-
-
Color
White
-
-
Finish
Powder-coated
-
-
Material
Steel, Copper, Aluminium
-
-
Shape
Rectangle
-
-
Length
1960 mm, 2304 mm, 3330 mm, 3221 mm
-
-
Width
1005 mm, 1060 mm, 1100 mm
-
-
Height
1340 mm, 1480 mm, 1510 mm
-
-
Warranty description
Two year
-
-

Specification

Classification data
Standards
-
-
-
Test requirements
To EN 14511-1.
-
-
Mode
Heating and cooling.
-
-
Coefficient of performance (minimum)
4.48 (COP); 4.54 (SCOP).
-
-
Energy efficiency
4.31 (EER); 4.81 (SEER).
-
-
Integrated service fittings
Inverter controlled primary circulation pump.
-
-
Output
-
-
-
Heating
26.1 kW.
-
-
Cooling
29.9 kW.
-
-
Fan
-
-
-
Type
Axial.
-
-
Fan drive
Direct.
-
-
Configuration
Manufacturer's standard.
-
-
Electrical supply type
Three-phase.
-
-
Compressor
-
-
-
Type
Rotary.
-
-
Sealing
Hermetically sealed.
-
-
Drive
Inverter-driven.
-
-
Sound power level
73 dB(A).
-
-
Environmental rating
A+++/A++.
-
-
Accessories
Not required., Additional board for advanced functions management., User side hydronic group with one inverter pump., Steel mesh strainer for primary return., Copper/ aluminium condenser coil with acrylic lining., Finned coil protection grilles., Anti-vibration mounts., Drain tray with electric element.
-
-
Refrigerant
R32.
-
-

Sustainability data

Material
Steel, Copper, Aluminium
-
-