NBS Source
I'm a manufacturer

Compare variants

Acti9 Three Phase Type B Distribution Boards
Acti9 Three Phase Type B Distribution Boards
Acti9 Three Phase Type B Distribution Boards

Verified 7 months ago

Schneider Electric Ltd

Verified 7 months ago

Schneider Electric Ltd

Verified 7 months ago

Schneider Electric Ltd
Summary
Range of three phase distribution boards.
-
-
Application

Suitable for standard, commercial and industrial applications for final circuit single phase or single phase and neutral low voltage distribution, typical loads serviced:

  • Motors, general power, HVAC, critical power.
-
-
Description

A range of three phase assemblies containing switching or protective devices (e.g. circuit breakers, Arc fault detection devices, and residual current devices) associated with one or more outgoing circuits fed from one or more incoming circuits, together with terminals for the neutral and circuit protective conductors. It may also include signaling and other control devices.


The evolution of low voltage electrical distribution continues with the demands for reliability, enhanced safety, cost reduction and connectivity ever increasing.


Through market leading innovations for over a quarter of a century, Isobar distribution boards have enabled this evolution and offered new levels of performance, several of which were the first of their kind:

  • Outgoing way disconnect feature;
  • Integrated neutral switching function;
  • Integrated incoming metering functions;
  • Integrated innovative Plug On Neutral distribution system;
  • Integration of AFDD into the three-phase distribution board;
  • Enhance safety with the Integration of an all-in-one Active AFDD into three-phase distribution board.


Active Safety System:

Advanced notifications, diagnostics, analytics, and a compact integrated device. It gives business owners and maintenance personnel greater control over their building's electrical health and, in turn, enhances service continuity.


The Plug On Neutral & Functional Earth residual current breakers with over-current (RCBOs) bring innovation for quick and easy installation, benefits include:

  • Time saving due to the quick and simple plug-on technology.
  • Fast and efficient due to absence of functional neutral and earth wires to unravel and straighten.
  • No need to cut, dress or terminate any functional wires.
-
-
Color
Cream
-
-
Shape
Rectangle
-
-
Warranty description
18 months
-
-

Specification

Classification data
Standards
To BS EN 61439-3; BS EN 60898-1; BS EN 61009-1; BS EN 61008-1; BS EN 60947-2; BS EN 62606.
-
-
Rated operational voltage (Ue)
230/ 240 V a.c., 400/ 415 V a.c.
-
-
Outgoing devices
-
-
-
Type
-
-
-
Busbars and connections
-
-
-
Type
Manufacturer's standard.
-
-
Rated current (InA)
250 A.
-
-
Rated short-time withstand current (Icw)
Manufacturer's standard.
-
-
Neutral and earth bars
Manufacturer's standard.
-
-
Neutral terminations
Manufacturer's standard.
-
-
Spare ways
Fit with blank plates., As circuit schedules.
-
-
Enclosure
-
-
-
Ingress protection (minimum)
To BS EN 60529, IP3X.
-
-
Material
Steel.
-
-
Finish
Powder paint.
-
-
Colour
Cream (RAL 9001).
-
-

Additional properties

Breaking capacity
25 kA.
-
-
Overvoltage
Category: IV.
-
-
Rated insulation voltage
500 V.
-
-
Rated impulse withstand voltage
6 kV.
-
-
Impact resistance
IK05.
-
-
OperationalTemperatureRange
-35 to 70°C.
-
-
Integral accessories
Meter kit.
-
-