NBS Source
ViLX-OSB Type B Refuge Outstation
Compare variants

ViLX-OSB Type B Refuge Outstation

Verified by manufacturer 4 months ago

VILX-OSB-G: Green Type B outstation

Vox Ignis Limited Variant:

Type B outstation that fits on any "MK"style double back-box over 25 mm deep.

Jump to:
+44 (0)191 516 6030 www.vox-ignis.com

Application

Lexicomm Emergency Voice Communications Systems (EVCS) are designed to fully comply with the requirements of BS 5839-9: 2021, for use as a fire telephone system (FT), disabled refuge system (DRS) or as a combined system when both fire telephones and disabled refuge call points are required.

Description

An EVCS is a fixed, secure, bi-directional, full duplex voice communication system to assist fire fighters and management during emergencies in high rise buildings or large sites, where radio communication cannot be guaranteed to work due to interference from the fire plasma. The ViLX-OSB is a type B outstation exclusively for use as part of a disabled refuge system, it’s fully compatible with the Lexicomm standalone and network systems.


The outstation is constructed from injection moulded green polycarbonate and features a green flashing button to aid location. Operation is via a single call/ cancel button, pressing it once activates the call, a second press cancels the call. The outstation should be installed in the disabled refuge area which is usually located in a protected stairwell/ stair lobby.


Features and benefits:

  • Modern compact design with high visible or brushed stainless steel appearance.
  • Fits in a standard UK style double socket backbox.
  • High volume ringer.
  • Green flashing call button for location.
  • Red status LEDs in call button.
  • Flush or surface mounted.
  • Braille enhanced call button.
  • Full duplex operation.
  • Up to 500m distance from a compatible panel

General information

Color

Silver

Green

Finish

Brushed

Material

Stainless steel

Acrylic

Polycarbonate

Shape

Rectangle

Length

22 mm

Width

86 mm

Height

146 mm

WarrantyDescription

18 months

Uniclass

Pr_75_75_94_23 Disabled refuge outstationsPrimary

CAWS

W53/635 Installing disabled refuge outstations

W53/335 Disabled refuge outstations

Product range

Outstations

Specification data - Disabled refuge outstations

Standard

To BS 5839-9, BS 9999, EN 55035: 2017+A11: 2020, EN 55032: 2015+A1: 2020.

Mounting type

Surface-mounted.

Flush.

Material

Polycarbonate.

Colour

Green.

Weight

155 g.

Height:

146 mm.

Width

86 mm.

Depth:

22 mm.

Type:

Enhanced/ Standard, Fire resistant.

Refer to BS 5839-9: 2021 for exceptions.

Cable

2 core, 1.5 mm screened.

Cable length

500 m.

Environmental information

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Britain.

Digital objects

Platform Compatible Version Certified to
IFC
-

1

2.1
Revit
-

1

2.1
Download now from NBS National BIM Library

Literature

ViLX-OSB-SS Type B outstation

ViLX-OSB-SS Type B outstation

ViLX-OSB-G, Green Type B Outstation

ViLX-OSB-G, Green Type B Outstation

Similar products from Vox Ignis Limited

ViLX-ILB Type B Refuge Outstation c/w induction loop

ViLX-ILB Type B Refuge Outstation c/w induction loop

VILX-IPA2 Weatherproof Type A IP66 Fire Telephone

VILX-IPA2 Weatherproof Type A IP66 Fire Telephone

ViLX-IPB2- Weatherproof IP66 Type B Refuge Outstation

ViLX-IPB2- Weatherproof IP66 Type B Refuge Outstation

ViLX-OSA Type A Fire Telephone

ViLX-OSA Type A Fire Telephone

ViLX-OSC Combined Type A and B Outstation

ViLX-OSC Combined Type A and B Outstation