Aspirating smoke detector with two pipes and docking station.
Smoke detection.
Model FIRElink-100 is designed to provide very high sensitivity smoke detection in a small package. A unique sensing technology ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup; This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.
The detector is designed to fit into a Docking Station which accepts all sampling pipes and cables leaving the detector to be fitted during the final commissioning phase. This ensures that the detector is less likely to be damaged during installation.
Volt-free Fire 1 and Fault relay outputs are provided for remote monitoring by local fire detection or BMS systems.
Features and benefits:
Color | Silver |
Finish | Powder-coated |
Material | Metal |
Shape | Rectangle |
Length | 85 mm Guidance for specification option: Depth |
Width | 300 mm |
Height | 225 mm |
Warranty description | Three year |
Uniclass | |
CAWS | W90/328 Point smoke detectors |
Standard | To BS EN 54-20. |
Sampling pipe | |
Arrangement | ¾” nominal bore (27 mm O/D) (EN 54-20 performances). |
Length (maximum) | 50 m ( 2 x 25 m or 1 x 35 m) moving air (>1 ms) or 100 m (2 x 50 m OR 1 x 65 m) still air (max). |
Air inlet holes (maximum) | Two. |
Power supply | 21.6–26.4 V d.c. |
Current | 400 mA at 24 V d.c. Guidance for specification option: Relay contact rating 500 mA at 30 V. |
Accessories | FL-PIPE Pipe 0.75 Diameter Nom Bore 3 m Length Red. FL-SR Socket Red. FL-90BR 90 Degree Bend Red. FL-45ER 45 DegreeElbowRed. FL-ECR End Cap Red. |
Material | Metal |
Expected Life | Ten year |