Aspirating smoke detector with four pipes and docking station.
Smoke detection:
Model FIRElink-400 is designed to provide very high sensitivity smoke detection using an aspirating technique. A unique sensing technology ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex set-up.
The detector is available in three formats, the standard detector (FIRElink-400), the standard detector plus Command Module (FIRElink-400CM) and a standalone Command Module (FIRElink-CM). The Command Module variants provide a single location display, control and interfacing option for systems of up to 127 detectors and allow global programming of all detector functions simultaneously.
Features and benefits:
Color | Silver |
Finish | Powder-coated |
Material | Metal |
Shape | Rectangle |
Length | 95 mm Guidance for specification option: Depth |
Width | 427 mm |
Height | 372 mm |
Warranty description | Three year |
Uniclass | |
CAWS | W90/328 Point smoke detectors |
Standard | To BS EN 54-20. |
Sampling pipe | |
Arrangement | ¾” nominal bore (27 mm O/D) (EN 54-20 performances). |
Length (maximum) | 100 m (2 x 50 m) still air (max).Guidance for specification option: Total sampling pipe maximum: 200 m at 100 sampling holes. |
Air inlet holes (maximum) | Four on top, Four on rear. |
Enclosure | |
Ingress protection (minimum) | IP50. |
Power supply | 21.6–26.4 V d.c. |
Current | 470 mA at 24 V d.c. Guidance for specification option: Relay contact rating 500 mA at 30 V. |
Accessories | FL-PIPE Pipe 0.75 Diameter Nom Bore 3 m Length Red. FL-SR Socket Red. FL-90BR 90 Degree Bend Red. FL-45ER 45 DegreeElbowRed. FL-ECR End Cap Red. |
Material | Metal |
Expected Life | Ten year |