Verified by manufacturer 19 days ago
H32-DLB
Thermostatic mixing systems.
Suitable for controlling temperatures in:
A range of DN32, DN40 and DN50 Horne thermostatic mixing valves that provide temperature control for larger dead-leg mixing applications or circulating domestic hot water systems (DHWS), and for circulating systems in conjunction with water treatment, such as ionisation.
Features and benefits:
* Append the relevant range code (e.g., T1) to your selected product variant, such as H40-RT4. Also note - If the intended output set temperature falls within more than one range (e.g., 60°C), choose the range where the set point is closer to the lower limit, thus T4. This reduces expansion fatigue on the thermostatic element, extending its operational life.
Color | Bronze |
Finish | Bronze Chrome |
Material | Gunmetal |
Shape | Other |
Uniclass | |
CAWS | S90/680 Thermostatic mixing valves |
Valve size | DN32 (1¼" BSP). |
Finish | Bronze. |
Integral accessories | Dial thermometer. |
Temperature | Guidance for specification option: Insert requirements.
|
Flow rate (maximum) | 2.5 L/s (150 L/min). |
Supply pressure | Hot and cold supply pressures to be nominally equal. |
Approval | Compliant with UK Water Regulation 4; non-metallic materials in contact with potable water. |
Country of product manufacture | United Kingdom |
Material | Gunmetal |
Manufacturing plant location | |
Recyclability | Recyclable |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 1 | |
- | 1 |
Horne 40 and Horne 50 Thermostatic Mixing Valves
H32-DL Dimensions
H32-R Dimension
H40-DL Dimensions
H40-R Dimensions
H50-DL Dimensions
H50-R Dimensions
Circulator Location for DHWS - Best Practice
Capacity Chart - Horne 32
Capacity Chart - Horne 40
Capacity Chart - Horne 50
Horne 32 Brochure
Instructions - Horne 32
Instructions - H40 & H50