NBS Source
I'm a manufacturer
Compare variants

Supercel® Alumen Air Duct Insulation - Phenolic Foam Boards

Verified by manufacturer 3 months ago

25 mm

MW Insulation Ltd Variant:

Phenolic foam boards for ducting applications.

Jump to:
+44(0)161 877 1608 Website

Application

For industrial and commercial ductworks, conditioned or unconditioned area ductworks, plenums and associated equipment.

Description

A high performance rigid thermoset designed for ductworks, especially those requiring non-fibrous material.


Supercel® Alumen Air comprises a phenolic resin foam insulation core with an external 25 micron aluminium vapour barrier foil facing reinforced by 5 mm glass scrim on the upper side and a saturated glass tissue facing on the lower side.


Features and benefits:

  • High performance.
  • Aluminium foil vapour barrier applied.
  • EN 14314 Phenolic foam standard compliant.
  • Fire safe - B-s1,d0 classification to EN 13501-1.
  • Thermally efficient - max aged K value of 0.021 W/m·k.

General information

Color

Silver

Pink

Finish

Foil

Glass tissue

Material

Phenolic foam

Shape

Rectangle

Length

600 mm

2400 mm

Width

1200 mm

Height

Warranty description

Other

Uniclass

Pr_25_71_63_59 Phenolic foam boardsPrimary
Pr_80_77_76_62 Phenolic foam insulation

CAWS

U90/490 Site-applied insulation to ductwork

Specification data - Phenolic foam boards

Fire performance

To EN 13501-1, B–s1,d0.

Thermal conductivity (maximum)

To EN 14314:2009+A1:2013, 0.021 W/m·K at 10°C.

Water permeability

To EN 1609, <1 kg/m².

Water vapour permeability

To EN 12086, >10.000 μ.

Compressive strength (minimum) at 10% compression

To EN 826, 150 kPa.

Cross section

Uniform thickness.

Thickness

25 mm.

Face size (length x width)

600 x 1200 mm.

2400 x 1200 mm.

Edges

Square.

Guidance for specification option:

Standard flat profile edges.

Facing

Aluminium foil faced and glass tissue.

Guidance for specification option:

25 micron aluminium vapor barrier foil reinforced by 5 mm glass scrim/ saturated glass tissue.

Dimensional stability

To EN 1604, ≤1.5%.

Guidance for specification option:

Thickness: 48 hrs at (70 ± 2) °C & relative humidity of (90 ± 5)%

Thickness: 48 hrs at -20°C.


Length & Width: 48 hrs at (70 ± 2)°C & relative humidity of (90 ± 5)%

Length & Width: 48 hrs at -20°C.



Closed cell content

To EN 4590, >90%.

TemperatureRange

-20°C to +120°C.

SpecificHeatCapacity

1750 J/kg·K.

Thermal resistance

1.15 m²K/W.

Thermal transmittance (U-Value)

0.84 W/m²K.

Sustainability data

Contains Red List materials

No

Country of material origin

Italy

Country of product manufacture

Italy

Material

Phenolic foam

Manufacturing plant location

Recyclability

NA

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

Literature

Supercel® Alumen Air Duct Insulation

Supercel® Alumen Air Duct Insulation