Verified by manufacturer 4 days ago
D (drive) version, D120 curtain
Certificate of constancy of performance
Certificate type
An automatically controlled smoke curtain designed to channel smoke, flames and combustion gases in the event of a fire. The curtain forms barriers and thus prevents the spread of smoke & gases.
Automatically controlled smoke curtain designed to channel smoke, flames and combustion gases in the event of a fire. The curtain forms barriers and thus prevents the spread of smoke and gases.
A SmokeMaster SM5 is a smoke curtain that drops automatically in case of fire. Its role is to limit smoke and combustion gases to prescribed smoke sections, preventing the uncontrolled spread and cooling of the smoke gas. A SKC-SC certified control panel ensures safe operation. The SmokeMaster SM5 is used in shopping centres, atria, airports, warehouses and factory buildings etc, in other words, wherever static smoke curtains are not suitable for architectural, logistical or operational reasons.
Product Highlights:
Product Technical Information
Dimensions:
Controls:
There are two actuator types available for the SM5: a D version (drive up, drive down version - ASB2/4) with 230V AC, as well as the G version (gravity down version - ASB1/3) with 48V DC motor and functional weight.
The unwinding mechanism of the G version is installed within the roller and contains, in addition to the high-quality DC motor with its planetary gears, a control board with its own intelligence for carrying out the essential safety-related functions:
Compliance:
Material | Glass Fibre |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Uniclass |
Product range |
Classification data | |
Standard | To BS EN 12101-1. |
Category | ASB2/4. |
Classification categories | D 120. Guidance for specification option: 600⁰C for 120 minutes. |
Material | D120 stainless steel-reinforced glassfibre. Guidance for specification option: The curtain material comprises a silver-grey glass fibre fabric with a fire-retardant aluminium-filled polyurethane coating to ensure good heat reflection.
|
Type | SI single roller unit. DH (double horizontal) unit. Guidance for specification option: Where there is a premium on space under the ceiling, where continuous runs with overlapped fabric to form a continuous barrier are required. DV (double vertical) unit. Guidance for specification option: Where continuous runs with overlapped fabric to form a continuous barrier are required. |
Dimensions | Manufacturer guidanceInsert requirements.
A requirement above these sizes will be met by installing either double horizontal or double vertical units. |
Controls | Drive down (D). Guidance for specification option:
|
Bottom bar | Bottom bar with weights, galvanized finish. Bottom bar with weights, powder-coated. Guidance for specification option: Insert colour requirements (RAL). Bottom bar with weights and spring, galvanized finish. Guidance for specification option: To accommodate any unevenness in the ceiling. Bottom bar with weights and spring, powder-coated. Guidance for specification option: To accommodate any unevenness in the ceiling. Insert colour requirements (RAL). |
Access panel | Galvanized steel. Guidance for specification option: Standard. Powder coated, RAL. Guidance for specification option: Consult manufacturer for options and insert requirements. |
Headbox | Galvanized steel. Guidance for specification option: Standard. Powder coated, RAL. Guidance for specification option: Consult manufacturer for options and insert requirements. Manufacturer guidanceHeadbox: 1.25 mm-thick galvanized steel. |
Side guides fixing | FR (rollers), end fixed. FR (rollers), face fixed. FR (rollers), flush fixed. FS (loops and rods), end fixed. FS (loops and rods), face fixed. FS (loops and rods), flush fixed. Manufacturer guidanceSide guides:
|
Material | Glass Fibre |