Verified by manufacturer 25 days ago
Warringtonfire
Certificate type
Active smoke barrier that deploys vertically to protect escalators and atria from smoke in standard commercial buildings.
Suitable for use in atria, lobbies and receptions, compartmentation, stairs and escalators, lifts and lift lobbies.
Is an active smoke barrier that deploys vertically to protect escalators and atria from smoke in standard commercial buildings. It suits all types of ceiling configurations to integrate with both solid and suspended ceilings. It remains hidden within a ceiling until deployed. It is supplied with the Coopers Total Gravity Fail Safe (TGFS) system, high temperature motors, side channels, variable speed, warning systems and controlled descent. Barrier assemblies shall be tested for fire resistance to BS EN 1363-1, tested for permeability BS EN 1634-3 as required by BS EN 12101-1:2005+A1:2006, and be classified to BS EN 13501-4.
Active smoke barrier assemblies shall comprise of a fire resistant fabric which is wound onto a steel roller, with 1:600 deflection performance to BS 6323-5, which is powered by an internal 24 V d.c. electric motor. They are enclosed within a 1.2 mm-thick galvanized carbon steel box. A bottom bar to suit the deflection performance requirements of the project and the desired ceiling configuration is fitted to the bottom edge of the fabric curtain.
Motors shall meet all applicable safety standards. Motors shall contain the necessary drive mechanisms, a mechanical epicyclic gearbox retarder, automatic overload protection and both automatic and manual distance travel positioning, linked to an internal 24 V d.c. electromagnetic brake with regenerative braking system. When motors are retracted, their internal drive motor shall be isolated from all power and the barrier shall be held in position by an internal electromagnetic brake. This ensures the barriers do not drift upward or downward.
The barrier assemblies shall operate with fail-safe by gravity, using patented Total Gravity Fail Safe (TGFS), in accordance with BS EN 12101-1:2005+A1:2006, and be able to move to their fire operational position even in the event of open or closed circuit wiring, or total system corruption, with controlled braking system and drive mechanisms. All working parts shall be totally enclosed and protected within the steel roller and shall be tested as part of the complete assembly for fire resistance.
The barrier assemblies must show the tested ability to use a range of heavy bottom bar weights in order to meet the critical anti-deflection performance requirements, as required in design guides BS 7346-4, BR 368. The bottom edge of the smoke barrier shall incorporate a heavy bottom bar with a minimum standard weight of 3 kg/m with the facility to increase this weight to 10 kg/m to ensure positive operation when subjected to pressure.
Operation:
The barrier assemblies type ASB1 and ASB3 for "Life Safety" shall move to their fire operational position in a controlled manner when all consumable primary and auxiliary power sources are removed, in the event of wiring, open or short circuit, or system corruption, or any combination thereof.
The barrier assemblies shall fail-safe by gravity, using patented true TOTAL (TGFS), and 'drive up' with mains power available. In the event of mains power failure, they shall remain retracted using their own dedicated battery back-up power supply for a pre-determined period (normally 30 minutes). If signalled to descend during this period, they shall fail-safe by gravity in a controlled manner to their fire operational position. This safety feature is essential to avoid dangerous guillotine/ free-fall deployment.
The barrier assemblies must commence movement upon initiation or any initiation, power or system failure and move to the fire operational position, in all operating modes, at site specific adjustable and synchronised velocities within the range of 0.06 m/s to 0.30 m/s using the unique VarioSpeed™ function. Barrier assemblies which are located in critical areas of the project, e.g. escape routes to have synchronised velocities within the range of 0.06 m/s to 0.15 m/s using the VarioSpeed™ function.
Operating speeds shall be site adjustable without altering bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for 'safety in use' according to the location, nature or function of each unit.
The barrier assemblies shall have the facility to deploy to a partial drop position prior to moving to their fire operational position under both mains and emergency power. Barrier assemblies in their retracted or 'stalled' position shall have all power removed from the motor(s) to prolong motor life. Barrier assemblies that require multiple overlapping barriers shall have a continuous bottom bar system conjoining the run with mutual operation, i.e. one down - all down (handshaking).
The barrier assemblies shall have a 'soft ascent facility' to ensure no damage to the surrounding ceiling interface when retracting. The barrier assemblies shall have a built-in protection in the event that they are prevented from ascending to their retracted position, or descending to their fire operational position. This ensures they are always in their required position and avoids damage to the barrier assemblies' mechanism and surrounding ceiling finishes. In sensitive ceiling aesthetic areas, a unique patented SLAT® ceiling interface can be provided. Any combination of the alarm/ control system provided by the electrical subcontractor, and/ or the specified fail-safe functions shall activate the system.
The barrier assemblies must prove the ability to operate within edge gaps between 20, 40 and 60 mm, height dependent, in all other situations unless the fabric edge interfaces with a retention system, i.e. side guides to resist pressure (as standard 25 Pa). If side guides are provided they shall have formed part of the complete system test in accordance with BS EN 12101-1:2005+A1:2006.
Period of fire resistance:
60 minutes integrity.
Complete barrier assemblies are CE marked in accordance with the EU Construction Products Directive (89/106/EEC).
Color | Other |
Finish | Galvanized |
Material | Fabric Guidance for specification option:
|
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year Guidance for specification option: From date of commissioning. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Standards | BS EN 12101-1+A1, BS EN 1363-1, BS EN 1634-3, BS EN 13501-4, BS EN ISO 1716, BS EN 13823, BS EN 13501-1, BS 476-6, BS 476-7. |
Barrier assemblies | To BS EN 12101. |
Test standards | To BS EN 12101. |
Third-party certification | Certifi - Warrington Fire. |
Size | Bespoke.Guidance for specification option: Consult manufacturer and insert requirements. |
Performance | |
Pressure and impact | SD. |
Durability class | C1. |
Smoke containment | To BS EN 12101. |
Fire resistance | 60 minutes. |
Reaction to fire | To BS EN 13501-4. |
Barrier units | Single.Multiple. |
Deployment | Full.Split drop delay. |
Accessories | None.Beam protection and obstruction warning.Emergency retract.Split drop delay.Visual alert system.Voice warning. |
Opening size | Guidance for specification option: Insert requirement, approved for spans unlimited in width, heights up to 10.5 m, minimum panel overlap 400 mm. |
Classification | DH60, A2-s1, d0, Class 0. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Recyclability | Coopers Fire offer a take back service where product is broken down into component parts. |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
Revit 2017 | 1 | |
- | 1 |
Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers
Fire Curtain - FireMaster® A1 ResQ-Window for Fire Curtain. - Fire Curtain Vision Panel
Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain
Fire Curtain - FireMaster® Concertina Open - L Shape - Concertina Fire Curtain - Fire Curtain Concertina
Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina
Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain
Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina
Fire Curtain - FireMaster® Plus² - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers
Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain
Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain