Verified by manufacturer 3 months ago
IFCC
Certificate type
An electrically operated active smoke barrier used to form a virtually continuous barrier against fire effluent.
Suitable to be used to form a virtually continuous barrier for a fire-separating element.
An electrically operated active fire curtain barrier assembly. Barrier assemblies comprises a metallic fabric, fan-folded and retained in a metal tray, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick steel box. A special bottom tray is fitted to the bottom of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’. The edges of the curtain are retained inside side guides, providing pressure resistance of 20 Pa. The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.
Barrier assemblies have been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08 m/s). Barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Fire Resistance’ (120 minutes' integrity). Barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Radiant Heat Flux’ (30 minutes).
The fabric used in the barrier assemblies have been tested to BS 476-6 and BS 476-7.
Operation:
Barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.
In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the barrier assembly will deploy.
Fire resistance:
180 minutes (3 hours) integrity (open).
Period of radiation:
55 minutes <15 kW/m² (open).
Classification:
E180 EW30 C1 Grade 1, A1.
Product certification, performance and/ or testing:
Approving standards:
The following standards apply to this product:
Color | Other |
Finish | Galvanized |
Material | Fabric Guidance for specification option: Metallic fabric. |
Shape | Circle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year Guidance for specification option: From date of commissioning. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Standards | BS 8524‑1:2013, BS EN 1634‑1:2014, BS EN 1363‑1:2012, BS EN 1363‑2:1999, BS EN 13501‑2:2007+A1, BS EN 14600:2005, BS EN ISO 1716:2010, BS EN 13501‑1:2007+A1:2009, BS EN ISO 14184‑1:2011, BS 6323‑5:1982, BS EN ISO 9001, BS EN ISO 14001, ISO Guide 65, BS EN ISO 17065, BS EN 1634‑1, BS 5234‑2, BS 8524‑1, BS EN 14600, BS 8524‑1, BS 8524‑1, S 8524‑1,BS EN ISO 1716. |
Barrier assemblies | To BS 8524-1. |
Test standards | To BS 8524-1, BS EN 1634-1 and UL 10D. |
Third-party certification | IFCC, Intertek, UL. |
Size | Guidance for specification option: Insert requirement, available in unlimited widths and drops up to 8.0 m. Manufacturer guidancePower supply size: 400 x 500 x 210 mm (w x h x d). Motor control unit size: 300 x 200 x 80 mm (w x h x d). |
Performance | |
Pressure and impact | SD. |
Durability class | C1. |
Smoke containment | Not applicable.Guidance for specification option: Only available on "closed" concertina fire curtains (specified separately). |
Fire resistance | 180 minutes (3 hours) integrity (open). |
Reaction to fire | To BS EN 13501-2, A1. |
Barrier units | Flexible metallic fabric, single.Flexible metallic fabric, multiple.Guidance for specification option: A concertina curtain can be made up of several barrier units all linked to create a conjoined shape. Insert the number of units/ sides required to give an indication of the size of the product. Manufacturer guidance
|
Deployment | Full. |
Activation | Commences movement upon initiation of alarm or power or system failure. |
Accessories | None.Beam protection and obstruction warning.Guidance for specification option: Will sound in the event of an obstruction being placed at the barrier drop line. Emergency retract.Guidance for specification option: Touch-button retract facility for multi-escape. Split drop delay.Guidance for specification option: Will partially deploy to pre-determined level to permit escape. Visual alert system.Guidance for specification option: Light warning system. Voice warning.Guidance for specification option: Auto-spoken multi-message facility. |
Classification | E180 EW30 C1 Grade 1, A1. |
Frame colour/ finish | Galvanized steel. Polyester powder-coated. Guidance for specification option: Insert colour requirements. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Recyclability | Coopers Fire offer a take back service where product is broken down into component parts. |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
Revit 2017 | 1 | |
- | 1 |