NBS Source
I'm a manufacturer

Single-Way Flat Interface

Verified by manufacturer 2 days ago

C-TEC (Computionics Limited)

A loop-powered single-way flat interface for use on a C-TEC EVAC-ALERT system controlling one or more evacuation alert devices located inside a flat.

Jump to:
+44 (0) 1942 322744 Website

Application

Applicable for use on a C-TEC EVAC-ALERT system suitable to control one or more evacuation alert device located inside a flat.

Description

A loop-powered single-way flat interface for use on a C-TEC EVAC-ALERT system.


Features and benefits:

  • Can control one or more evacuation alert devices located inside a flat.
  • Reliable hard-wired technology (for C-TEC’s position on wireless devices click here).
  • Compatible with the self-test facility on C-TEC’s BF430/EA and BF433C/EA range of self-testing evacuation alert devices.
  • Provides one open and short circuit fault monitored conventional sounder circuit (faults are indicated on the CA736 and reported back to the host EVAC-ALERT panel).
  • Mounts on a standard UK 35 mm double gang back box outside the flat for BS 8629 Clause 8 compliance.
  • 50 mA alarm current – can power up to eight evacuation alert sounders (most sites require only one alert sounder so this allows additional alert devices to be connected, e.g. for the hard of hearing).
  • Polling, sounder circuit active and input fault indicators.
  • On-board short circuit loop isolator.

General information

Color

Grey

White

Red

Finish

Other

Material

PVC

Shape

Rectangle

Length

22 mm

Manufacturer guidance

Depth.

Width

147 mm

Height

87 mm

Uniclass

Pr_75_80_30_41 Interface panelsPrimary
Pr_75_80_30_28 Fire alarm input and output modules

CAWS

W90/120 Fire detection and alarm systems in domestic premises

Specification data - Interface panels

Standards

To EN 50130-4: 2011+A1:2014 Alarm Systems – Part 4.

Dimensions

147 x 87 x 22 mm.

Manufacturer guidance

Width x height x depth.

Weight

0.16 kg.

Body

PVC.

Finish

ABS polycarbonate plate with 200 μm two-tone grey velvet polyester label with red and white detailing.

Ingress protection

IP40.

Guidance for specification option:

Indoor use only.

Humidity

Maximum 95% RH (non-condensing).

Operating temperature

-10°C to +55°C.

Indicator colour

Active: (steady red LED).
Polling (flashing red LED).
Fault (steady yellow LED).

Guidance for specification option:

Active - sounder circuit activated.

Polling - communication check with the control and indicating equipment (CIE).

Fault - wiring fault (open or short circuit) detected on the monitored sounder circuit.

Operating voltage

18–40 V d.c.

Current

Quiescent current: 530 µA.
Alarm current: 50 mA.

Monitoring

27 Ω end of line (EOL) short circuit (S/C) and open circuit (O/C) monitored.

Protocols

CAST®.

CAST®-PRO.

Sustainability data

Country of product manufacture

United Kingdom

Material

PVC

Literature

Datasheet for C-TEC's CA736 Single-Way Flat Interface

Datasheet for C-TEC's CA736 Single-Way Flat Interface

Similar products from C-TEC (Computionics Limited)

4-8 Way Flat Interface

4-8 Way Flat Interface