Verified by manufacturer 2 days ago
OSI-RE (reflective - 12° lens)
Beam smoke detector using optical imaging technology.
Suitable for a range of application areas, for example:
Beam smoke detector using optical imaging technology.
Available in the following configurations:
Features and benefits:
OSID-DE:
OSI-RE:
Color | White |
Shape | Other |
Length | 96 mm Guidance for specification option: OSID-DE. 114.3 mm Guidance for specification option: OSID-R. Manufacturer guidanceDepth. |
Width | 208 mm Guidance for specification option: OSID-DE. 254 mm Guidance for specification option: OSID-R. |
Height | 136 mm Guidance for specification option: OSID-DE. 152.4 mm Guidance for specification option: OSID-R. |
Uniclass | |
CAWS | W90/329 Optical beam smoke detectors |
SKU Code | OSI-RE |
Classification data | |
Standard | To BS EN 54-12. |
Third-party certification | ActivFire, VdS, NF-SSI, BOSEC-approved. |
Detector type | Reflected. |
Operating range (minimum) | 5–100 m. |
Ingress protection (minimum) | IP 44. Guidance for specification option: IP 44 for electronics. IP 66 for optics enclosure. |
Controller | |
Display type | Light-emitting diode display (LED). |
Display the following information | Red LED – fire alarm. Bi-colour yellow/ green LED – trouble/ power. |
Functions | Automatic and manual beam alignment. Guidance for specification option: OSID-DE: Up to 10 000 events stored. |
Power source | Wired. |
Weight | 1.12 kg. |
Power supply | 12 V d.c. 24 V d.c. |
Power consumption | 54 mA (maximum). |
Operating temperature | -20 to +55°C. |
Operating humidity | 0–95% RH, non-condensing. |
Sensitivity | Manufacturer's standard. Guidance for specification option: OSID-DE:
|
Cable | Gauge: 2.08 mm². |
Lens | 12°. Guidance for specification option: Adjustment angle: +/- 50° (horizontal). +/- 20° (vertical). |
Accessories | Not required. Wire guard - OSI-RWG. Image reset station (surface mount) - RTS151KIT. Image reset station (flush mount) - RTS151KEY. |