NBS Source
I'm a manufacturer

NV LogiQ PSU

Verified by manufacturer over a year ago

SE Controls

Adaptive environmental ventilation, single-zone control panel that can be networked in multi-zone projects.

Jump to:
+44 (0)1543 443060 Website

Application

  • Suitable for environmental ventilation applications.
  • The physical size and appearance has been designed to enable surface mounting for new and refurbishment projects.

Description

Adaptive environmental ventilation, single-zone control panel that can be networked in multi-zone projects.


Features and benefits:

  • The control panel can be linked directly to the NVLogiQ Room Controller to operate the Automatic Opening Vents (AOVs), based on changing internal and external conditions. Acts as the Building Management System (BMS), to provide a specific adaptive environmental ventilation control strategy for the building environment.
  • Alternatively, the NVLogiQ PSU can operate on a stand-alone basis operating on manual switches, or can be connected to the BMS to operate the AOVs as required.
  • Can be installed into new and refurbished buildings, where there is a focus on indoor air quality and energy saving.
  • Made in Britain.
  • CE marked.

General information

Shape

Rectangular

Color

White

Size

251.15 x 191.2 x 56.3 mm

Guidance for specification option:

Excluding glands.

Uniclass

Pr_75_50_18_51 Mechanical services control panelsPrimary

CAWS

S92/410 Sprinkler alarm panels

S92/410 Control panels

Specification data - Mechanical services control panels

Enclosure

-

Ingress protection (minimum)

IP20.

Colour

White.

Isolator

-

Rated operational current (In)

4.8 A.

Guidance for specification option:

Maximum actuator run current.

Rated operational voltage (Ue)

230 V a.c.

Rated operational frequency

50/ 60 Hz.

Guidance for specification option:

Supply from a fused un-switched spur.


Cable entry

Via five 20 mm end-mounted cable glands.

RelativeHumidity

10–90% (non-condensing).

TemperatureRange

Storage: -20 to +75°C, Operating: -10 to +50°C.

Class

Power: Class 1.

Power input

3.5 A: 100–120 V a.c., 2.0 A: 200–240 V a.c.

Guidance for specification option:

For 115 V a.c. operation, the mains input voltage selection switch must be set on the internal power supply.


Battery back-up

-

Manufacturer guidance

Real time clock battery (ten year average life).

Amps (starting)

Derate linearly to 70% load from +50 to +70°C.

Manufacturer guidance

Start-up peak current needs to be considered and can vary depending on actuator type.


SignalTime

2 s (0–10 V signals).

Guidance for specification option:

  • 0-10 V signals must remain stable and ‘spike’ free for a period of 2 seconds before the controller will respond to them.
  • In 10% step mode, the controller only responds to 0–10 V signals in steps of whole volts ±250 mV.
  • In 5% step mode, each step is 0.5 V. 


Sustainability data

Country of product manufacture

United Kingdom

Literature

SE Controls Product Specification Guide

SE Controls Product Specification Guide

Similar products from SE Controls

Fan Control Panel

Fan Control Panel

OS Loop Coordinator

OS Loop Coordinator

OS2 PSU

OS2 PSU

OS2 SHEVTEC Control Panel

OS2 SHEVTEC Control Panel

SHEVTEC® Repeater Panel

SHEVTEC® Repeater Panel