NBS Source
I'm a manufacturer

LPAV865 Loop Powered Symphoni Addressable Sounder Beacon IP65 Red Body Red Flash VID

Verified by manufacturer 2 months ago

ADT Fire and Security

Loop powered Symphoni addressable beacon sounder IP65 red body red flash VAD.

Jump to:
Website

Application

For use with Simplex 4100ESi fire alarm control panels equipped with the 4098-6077AU/LIM MX Digital Loop Card.

Description

MX Loop Powered Sounder-Beacons use MX TECHNOLOGY communications for control and power. Indoor models are available in red or white.


The outdoor model is in red. With these loop powered sounder-beacons, supervision is accomplished using MX loop communications and the beacon and sounder can be separately activated from the MX Control Panel.


The Tone and Beacon flash rate is selected at the Sounder-Beacon using the MX 850EMT Engineering Management Tool.


Features and benefits:

  • MX Loop powered with internal short-circuit isolator, separate voltage is not required
  • Available for outdoor mounting in red
  • Sounder-Beacons include a matching surface mount box with tamper resistant latch (release tool is included).
  • Selectable output volume of 90 or 103 dB.
  • Sounder-Beacons on the same MX Loop are synchronized when using the 4100ESi coding option
  • Output tone patterns are selectable from 16 choices including: Temporal3 (880 Hz), Slow Whoop (500 to1200 Hz), conventional Bell, or Continuous
  • Beacon flash rate selectable: 1/2Hz or 1Hz
  • Address; sounder tone and volume; and beacon flash rate selections are easily programmed with the MX 850EMT Engineering Management Tool.

General information

Color

Red

Shape

Other

Length

110 mm

Width

105 mm

Height

110 mm

Uniclass

Pr_75_80_30_30 Fire alarm soundersPrimary

CAWS

S92/420 Alarm devices

Specification data - Fire alarm sounders

Standard

To BS EN 54-3 and EN 54-23.

Sounder type

Electronic sounder.

Rated voltage

Guidance for specification option:

  • Quiescent 0.45 mA.
  • Sounder Beacon 7.6–13 mA (dependent on volume and flash rate).

Enclosure protection

IP65.

Sound pressure level (minimum)

Selectable output volume of 90 or 103 dB.

Integral beacon

To BS EN 54-23, O.

Mounting

Surface.

Power supply

From loop.

RelativeHumidity

Up to 95% RH (non condensing).

Operating temperature

-20 to +70°C.

BIM objects

Platform Compatible Version
Revit
-

1

Literature

516.800.965 LPAV865 Loop Powered Symphoni Addressable Sounder Beacon IP65 Red Body Red Flash VID

516.800.965 LPAV865 Loop Powered Symphoni Addressable Sounder Beacon IP65 Red Body Red Flash VID

Similar products from ADT Fire and Security

LPBS865 Open Class Symphoni Addressable Beacon Sounder IP65 Red Body White Flash VAD

LPBS865 Open Class Symphoni Addressable Beacon Sounder IP65 Red Body White Flash VAD

LPSY865 Loop Powered Symphoni Addressable Sounder IP65

LPSY865 Loop Powered Symphoni Addressable Sounder IP65

P82AVB Addressable OC Base Sounder Beacon

P82AVB Addressable OC Base Sounder Beacon