This site uses cookies to store information on your computer. Learn more about these cookies, and how to opt out of them. Find out more

NBS Source

Application

Suitable for fire rated mechanical smoke extraction shafts in multi-storey buildings.

Description

Lobby smoke damper designed to satisfy smoke vent applications. It has been fire tested to the latest European fire damper test standard BS EN1366-2, and achieves a two-hour fire resistance performance to ES120.

The units are fitted in the wall between a lobby or corridor into a vertical smoke shaft. The top of the damper should be as high as possible but can be fitted at the same height as the head of the architrave.


Features and benefits:

  • Longevity cycle tested for 100 000 fully open closed operations.
  • 24 V AC/ DC Belimo BE motor open/ motor closed actuator.
  • Actuator is on lobby side, hidden from view behind painted cover plate and can be manually operated if needed.
  • Easy access to actuator by simple removal of cover plate behind grille.
  • Volt free monitoring contacts.
  • Can also be used for environmental control.
  • Simple to install.

General information

Color

White

RAL 9010.

Black

Inside of damper.

Material

Steel

Size

Insert requirement, available 400–1200 x 400–1500 mm in 100 mm increments.

Length

Bespoke

Width

Bespoke

Height

Bespoke

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire and smoke

U90/443 Dampers, fire and smoke

Specification data - Fire and smoke dampers

Standard

-

Test

To BS EN 1366-2.

Classification

ES120.

Material

Steel.

Grille colour

Entire inside of damper behind grille is spray painted matt black, fixing screws are colour matched to the grille.

RAL 9010 White.

Standard.

Special order.

Insert requirement.

Frame

1.5 mm thick galvanized steel frame.

With fully seam welded corners along the entire depth to produce a rigid and air tight construction.

Damper

Damper blades.

0.7 mm thick galvanized double skin airfoil.

Vertical 'opposed motion' to enhance air entrainment being ‘pulled’ into in smoke shaft. 0.7 mm thick galvanized double skin airfoil, 100 mm pitch with interlocking engagement when damper is closed.

Gasket

0.4 mm grade 301 stainless steel..

Peripheral gasketing around the entire perimeter.

Drive

‘Out of airstream’ mechanism.

LeakageClass

Ambient leakage (To BS EN 1366-2/ ISO10294-2).

Conforms to class ES (200 m³/hr/m² – 55 L/s/m²).

Fixing

Pre-punched damper sleeve fixing holes.

Dimensions

Insert requirement, available 400–1200 x 400–1500 mm in 100 mm increments.