Gas 620 Ace 570

BAXI HEATING UK LIMITED Variant:

Compact, floor-standing, gas-fired high efficiency condensing boilers.

Jump to:
0330 678 0140 Website

Application

Suitable for commercial use, for both new and retrofit applications.

Description

Engineered for reliable and efficient performance, the Gas 620 Ace floor-standing boiler is designed with new and old building plant rooms in mind. It’s a compact boiler, easy to install and easy to maintain. The Gas 620 Ace has the capacity to be installed side to side, which provides flexibility in floor design. It also has an optional secondary return feature that makes this boiler particularly suitable with heating technologies that use low-grade heat, such as heat pumps or underfloor heating circuits.

Features and benefits:

  • Operating range - ΔT of 10–40°C, operating range of 20°C to 80°C and maximum set point of 90°C.
  • Low to zero - low to zero-flow condition operation and monitoring, low-water content.
  • Connection to BMS - Modbus gateway option for connection to a BMS system.
  • Enhanced connectivity - Bluetooth for enhanced connectivity.
  • Low emissions - NOx emissions from 15 mg/kWh.
  • Highly efficient - condensing efficiency up to 106.8% and non-condensing efficiency up to 98.5%.

General information

Color

Red

Black

Finish

Smooth

Material

Aluminium

Shape

Rectangle

Length

1862 mm

2172 mm

Width

1442 mm

Height

1726 mm

1550 mm

Warranty description

Seven year

Uniclass

Pr_60_60_08_34 Gas-fired condensing boilersPrimary

CAWS

T90/312 Boilers, gas-fired condensing

Specification data - Gas-fired condensing boilers

Classification data

Standards

-

Boilers with heat input greater than 70 kW but not exceeding 1000 kW

To BS EN 15502-1.

Output

75.8–521.4 kW (80/60℃); 557.5 kW (50/30℃).

Seasonal efficiency (gross calorific value (minimum))

96.48%.

NOx emissions (maximum)

43 mg/kW·h.

Guidance for specification option:

  • Dry, 0% O₂ - Class 6.
  • NOx Annual Emissions BREEAM – NG: 15 mg/kW·h.

Manufacturer guidance

NOx Annual Emissions EN 15502 – NG.

Mounting

Floor mounted.

Operating pressure

7 bar (maximum); 0.8 bar (minimum).

Operating temperature

20–90℃.

Heat exchanger

Aluminium.

Fuel

Natural gas.

Guidance for specification option:

  • Standard fuel.
  • Fuel consumption (maximum): 56.3 m³/h.
  • Gas connection size: 2" male BSP.
  • Gas pressure: 17–25 mbar.

Electrical supply type

Single phase.

Guidance for specification option:

230 V, 50 Hz (x2).

Accessories

-

Manufacturer guidance

Consult manufacturer for details and insert requirements or omit.

Power consumption

10–280 W per module.

Fuse rating

10 amps (x2).

Ingress protection (IP) rating

IP X1.

Dimensions

1442 x 1726 x 1862 mm.

Manufacturer guidance

Overall dimensions (width x heigh x depth).

Weight

711 kg.

Manufacturer guidance

Weight (dry) without packaging.

Sustainability data

Contains Red List materials

No

Country of product manufacture

Netherlands

Manufacturing plant location

Material

Aluminium

Expected Life

20 year