A multifunctional and customizable water, oil and gas leak detection control panel.

Jump to:
+44 (0)1484 845000 Website

Application

Suitable for multi-zone use.

Description

Multi-zone control panel with options of four, eight or sixteen zones.


The control panel continuously monitors a network of multiple leak detection zones (a zone can be anything from a single point to multiple liquid, gas and oil sensors, as well as liquid leak detection distance measuring up to 1500 metres via Andel’s Floodline Ranger® System).


The whole network is continuously monitored for leaks and continuity. Temperature and humidity sensors can be configured for four separate alarm levels in any zone. Zones are isolated from each other and individually displayed, so the system can accept and report any number of simultaneous or consecutive zone alarms delivering true multiple leak reporting. If an alarm is triggered in any zone, other zones remain unaffected, providing continuous leak detection.


A leak detection alarm is indicated by a flashing LED as well as an audible alarm with mute function. All alarms are displayed separately and continuously until corrected and reset.


Output relays connect to building management systems (BMS) and remote alarms and can drive other devices such as beacons and valves to isolate water, gas and oil supply in the event of a leak alarm.


Features and benefits:

  • Four-zone, eight-zone and sixteen-zone options.
  • Monitors the full range of Floodline® leak detection sensors, including liquid leak detection distance measuring up to 1500 metres via Andel’s Floodline Ranger® System.
  • Monitors temperature and humidity sensors.
  • In the event of an alarm, all other zones remain unaffected, providing continuous full leak detection monitoring and reporting.
  • LEDs provide clear system status and alarm information.
  • Audible alarm with mute function.
  • Output relays connect to BMS and remote alarm.
  • Includes controls for mute (buzzer silence/ alarm accept) button, security key-switch output disable/ reset.

General information

Color

Grey

Finish

Powder-coated

Material

Steel

Shape

Rectangle

Length

90 mm

Guidance for specification option:

Depth.

Width

285 mm

Height

292 mm

Warranty description

Ten year

Uniclass

Pr_75_50_18_48 Liquid presence detection programmable control unitsPrimary
Pr_75_50_18_33 Gas detection control panels

Specification data - Liquid presence detection programmable control units

Nominal voltage

230 V a.c.

Guidance for specification option:

110/230 V.a.c., 12 V.d.c. internal and battery backup.

Nominal frequency

50/ 60 Hz.

Guidance for specification option:

Mains operated, 25 W.

Number of zones

Four.

Eight.

Sixteen.

Controls

-

Display type

Status LEDs.

Guidance for specification option:

Flashing LEDs – all alarms displayed separately and continuously until corrected.

Status indicators for mains power supply, battery operation, internal 12 V d.c. supply, low battery, alarm accept (mute).

Display the following information

System fault.
Zone where the leak has occurred.

Guidance for specification option:

  • System fault: Sensor or leader cable damage, failure or disconnection.
  • Leak: Continuous water, gas and oil leak detection with each zone reporting separately.

Audible indication

Audible alarm.

Guidance for specification option:

Includes mute function.

Event log

Location.

Features

Remote alarm.

Communications

-

Outputs

Leak in any zone.
System fault in any zone.
Complete power fail.
Leak in individual zones.

Guidance for specification option:

  • Leak in any zone – double pole changeover (DPCO) relay (5 A at 230 V.a.c.).
  • System fault in any zone – single pole changeover (SPCO) relay (5 A at 230 V.a.c.).
  • Complete power fail – SPCO relay (5 A at 230 V.a.c.).
  • Leak in individual zones – SPCO relay – optional (1 A at 30 V.d.c.).


All relays have clean volt-free contacts.

Enclosure

-

Material and finish

Steel, powder-coated.

Guidance for specification option:

Fine textured, colour RAL 7043.

Mounting method

Suitable for walls.

Guidance for specification option:

Can be wall or surface mounted.

Accessories

-

Manufacturer guidance

Consult manufacturer for details and insert requirements.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom