FireMaster® 4/1000
Application

Lobbies and receptions, opening in walls, egress and corridor separations, stairs and escalators, lifts and lift lobbies.

Product certification, performance and/ or testing:

  • FireMaster® 4/1000 active fire curtain barrier assemblies are certified by an independent accredited certification body operating to ISO/IEC 17065:2012.
  • FireMaster® 4/1000 active fire curtain barrier assemblies have been tested for fire resistance to BS EN 1634-1. The Barrier assembly achieved 240 minutes Integrity and 30 minutes Radiation.
  • Motor(s) used within FireMaster® 4/1000 active fire curtain barrier assemblies have been tested for operation at temperatures of 400 °C as required by BS 8524-1
  • The fabric used in the FireMaster® 4/1000 active fire curtain barrier assemblies have been tested to BS 476 pt6 & pt7
  • The fabric used in the FireMaster® 4/1000 active fire curtain barrier assemblies have been tested to BS 6853
  • The fabric used in the FireMaster® 4/1000 active fire curtain barrier assemblies have been classified as ‘A1 to EN 13501-1

Approving standards:

The following standards apply to this product:

  • BS EN 1634-1:2008, Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows
  • BS EN 1363-1:2012, Fire resistance tests – Part 1: General requirements
  • BS EN 1363-2:1999, Fire resistance tests – Part 2: Alternative and additional procedures
  • BS EN 13501-2:2007+A1, Fire classification of construction products and building elements. Classification using data from fire resistance tests, excluding ventilation services rating
  • BS 476-6, Method of test for fire propoagation for products
  • BS 476-7, Method of test to determine the classification of the surface spread of flame for products
  • BS 6853: 1999 – Annex D.8.4, Methods for measuring smoke density
  • BS EN 13501-1:2007+A1:2009, Fire classification of construction products and building elements. Classification using test data from reaction to fire tests
  • BS EN ISO 14184-1:2011. Textiles. Determination of formaldehyde. Free and hydrolised formaldehyde (water extraction method)
  • BS EN ISO 9001:2015, Quality management system
  • BS EN ISO 14001:2015, Environmental management system

Description

An electrically operated FireMaster® 4/1000 active fire curtain barrier assembly used to form a virtually continuous barrier as a fire separating element.

FireMaster® 4/1000 active fire curtain barrier assemblies comprise a woven steel and glass fabric wound on to a steel roller, powered by an internal 24V dc electric motor, enclosed within a 1.2 mm Stainless Steel box.

A bottom bar is fitted to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.

The 24V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position

FireMaster® 4/1000 active fire curtain barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Fire Resistance’ (240 minutes integrity).

FireMaster® 4/1000 active fire curtain barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Radiant Heat Flux’ (30 minutes).

Operation:

FireMaster® 4/1000 active fire curtain barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function.

Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.

In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the Barrier assembly will deploy.

Fire resistance:

240 minutes (4 hours) integrity (single)

Radiation resistance:

35 minutes <15kW/m2 (single)

Classification:

E240 EW30 C0

Certification:

Complete barrier assemblies are certified by an independent accredited certification body operating to ISO/IEC 17065:2012.

Complete barrier assemblies are certified with an independent accredited certification body operating an accredited UKAS scheme for installation, commissioning and servicing.

Application:

Lobbies and receptions, opening in walls, egress and corridor separations, stairs and escalators, lifts and lift lobbies.

Product certification, performance and/ or testing:

  • FireMaster® 4/1000 active fire curtain barrier assemblies are certified by an independent accredited certification body operating to ISO/IEC 17065:2012.
  • FireMaster® 4/1000 active fire curtain barrier assemblies have been tested for fire resistance to BS EN 1634-1. The Barrier assembly achieved 240 minutes Integrity and 30 minutes Radiation.
  • Motor(s) used within FireMaster® 4/1000 active fire curtain barrier assemblies have been tested for operation at temperatures of 400 °C as required by BS 8524-1
  • The fabric used in the FireMaster® 4/1000 active fire curtain barrier assemblies have been tested to BS 476 pt6 & pt7
  • The fabric used in the FireMaster® 4/1000 active fire curtain barrier assemblies have been tested to BS 6853
  • The fabric used in the FireMaster® 4/1000 active fire curtain barrier assemblies have been classified as ‘A1 to EN 13501-1

Approving standards:

The following standards apply to this product:

  • BS EN 1634-1:2008, Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows
  • BS EN 1363-1:2012, Fire resistance tests – Part 1: General requirements
  • BS EN 1363-2:1999, Fire resistance tests – Part 2: Alternative and additional procedures
  • BS EN 13501-2:2007+A1, Fire classification of construction products and building elements. Classification using data from fire resistance tests, excluding ventilation services rating
  • BS 476-6, Method of test for fire propoagation for products
  • BS 476-7, Method of test to determine the classification of the surface spread of flame for products
  • BS 6853: 1999 – Annex D.8.4, Methods for measuring smoke density
  • BS EN 13501-1:2007+A1:2009, Fire classification of construction products and building elements. Classification using test data from reaction to fire tests
  • BS EN ISO 14184-1:2011. Textiles. Determination of formaldehyde. Free and hydrolised formaldehyde (water extraction method)
  • BS EN ISO 9001:2015, Quality management system
  • BS EN ISO 14001:2015, Environmental management system

General information

Finish

Galvanized

Powder coated

Available upon request, insert colour requirements.

Material

The main curtain fabric type is EFP™ 4/1000, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 690g/m2 -5% +10%

The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire

The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance)

The fabric has passed testing to BS 6853 (Methods for measuring smoke density)

The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos)

Show more

WarrantyDescription

One year

Uniclass 2015

Pr_30_59_84_73 Roller shuttersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Roller shutters

Product Reference

FireMaster®

Standard

Compliant to PAS 121:2007 (where applicable)

Opening sizes

Insert requirements.

Frame and guides

-

Material

Steel

Finish

Galvanized

Powder coated

Available upon request, insert colour requirements.

Side channels

-

Type

End fixed

Face fixed

Recessed fixed

Recommended 5 mm gap between side guide and building material.

Orientation

Vertical

Concealment

Flush fit

Suspended ceiling with recessed shallow gap

Suspended ceiling with patented SLAT™

Self levelling access trim.

Fixing

Face fixed

I beam

Soffit

Suspended with unistrut fit

Accessories

None

Beam protection and obstruction warning

A beam detector, with delay timer which will sound in the event of any obstruction being placed in the barrier drop line when mains or emergency power is available.

Emergency retract

Touch button retract facility for multi-escape and emergency services entry when mains or emergency power is available.

Split drop delay

To partially deploy to pre-determined level to permit escape, and initial smoke containment. After delay fully deploys to its fire operational position when mains, or emergency power is available.

Visual alert system

Light warning system when mains or emergency power is available.

Voice warning

Audio or spoken multi message facility when mains or emergency power is available.

Standard product features

Material:

The main curtain fabric type is EFP™ 4/1000, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 690g/m2 -5% +10%.

The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire.

The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance)

The fabric has passed testing to BS 6853 (Methods for measuring smoke density)

The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos)

The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method)

Warranty description:

One year.

Country of manufacture:

United Kingdom.