Two Hour Fire and Radiant Heat Resisting Curtain.
Fire curtains suitable for any internal application where fire compartmentation is required but is particularly suited for retail malls, offices, receptions, foyers, lift lobbies, lift Doors, open-plan private residencies.
These fire curtains are specifically designed to provide fire compartmentation and a protected means of escape all within a compact, aesthetically pleasing yet robust and reliable system.
Utilising a fully tested woven glass fabric with stainless steel wire reinforcement, the Fibreroll E120 Rolling Fire Curtain provides not only up to two-hour fire integrity between fire compartments but also a reduction in radiated heat to such a large extent that it meets the requirements for a rating of EW30, including Rigid Structures
and Flexible Structures
Features and benefits:
Color | Grey |
Finish | Galvanized Powder-coated Textured Manufacturer guidanceSide guides, bottom rail and coil casing supplied with polyester powder coated finish to alternative RAL colour from standard range. |
Material | Steel |
Shape | Square Rectangle |
Length | Bespoke |
Width | Bespoke Guidance for specification option: Bespoke sizes. Single roller - maximum 5000mm wide Multiple rollers - maximum width is unlimited |
Height | Bespoke Guidance for specification option: Bespoke sizes. Single roller - maximum 8000mm high Multiple rollers - maximum 6000mm high |
Warranty description | One year |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Product range |
Standards | Tested to EN 1634-1 and EN 1634-3 all in accordance |
Test standards | Vertical, horizontal and angled to BS EN 1634-1 and -3. |
Size | 5000 x 8000 mm.Manufacturer guidanceInsert requirement. |
Performance | |
Pressure and impact | Manufacturer's standard. |
Durability class | Manufacturer's standard. |
Smoke containment | Smoke tight seal. |
Fire resistance | E30.E60.E120.Guidance for specification option: Available up to 16254 x 6740 mm (clear width x clear height). EW30. |
Deployment | Two stage.Delayed descent. |
Activation | In a fire condition, activation is initiated by a normally closed volt free contact from the fire alarm system or, where on a fire exit route, local heat detector. Closure is by gravity with a controlled descent. |
Accessories | None.Emergency retract.Local heat detector.Obstruction warning (via light curtain).Sounder beacon.Two-stage descent.Voice warning. |
Execution | Installing active fire curtain barrier assemblies. |
Colour | Galvanised Steelwork PPC Option Available |
Fixing | Face-fixed. Soffit-fixed. Suspended (to a maximum of 500 mm). |
Weight | Curtain: 0.78 kg/m², Barrel/casing: 30 kg/m² (approx). Guidance for specification option: Approximately. |
Radiation | Reduction of 15kW/m² to EW30 classification. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Manufacturing plant location | Bolton BL1 2SP, UK |
Recyclability | 50% |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |