Verified by manufacturer 12 days ago
Design .01 - Manual control and thermal
Hygiene requirements to VDI 6022
Certificate type
DoP
Certificate type
Certificate of constancy of performance
Certificate type
EPD
Certificate type
A manual or motorised fire damper for air conditioning ducts.
The fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions. The fire damper can be installed into:
Additional applications may be available, please reference product Technical Specifications for more detail.
A Fire Damper is used to prevent fire and reduce smoke spreading from one compartment to another through the air ductwork system which may penetrate fire separating walls and floors
Features and benefits:
Color | Silver |
Finish | Galvanized |
Material | Steel |
Shape | Circle |
Length | 300 mm 500 mm |
Width | 100 mm 125 mm 140 mm 150 mm 160 mm |
Height | 100 mm 125 mm 140 mm 150 mm 160 mm |
Warranty description | Two year |
Uniclass | |
CAWS | U90/443 Dampers, fire/ smoke |
Standard | |
Fire dampers | To EN 15650. |
Test | To EN 1366-2. |
Classification | To EN 13501-3. |
Aerodynamic performance | To BS 1751.Guidance for specification option: Damper body: Class C; Damper blade: Class 3. |
Arrangement | Single-blade. |
Classification | EIS60.Manufacturer guidanceRefer to the manufacturer's literature for placement and installation details to achieve the fire resistance value. |
Material | Zinc-coated steel. |
Fusible links | |
Fusing temperature | 72°C.Guidance for specification option: As standard. 104°C.147°C. |
Spare fusible links | Manufacturer guidanceInsert requirements or omit. |
Design | Spiro damper (SL). Spiro damper, with installation brackets (SK). |
Actuator | Manual. |
Diameter | 100 mm. 125 mm. 140 mm. 150 mm. 160 mm. |
Length | Manufacturer guidance300–500 mm. Insert requirements or refer to a drawing. |
Duct connection | Mandik FFDM breakaway joint. Guidance for specification option: FFDM allows a breakaway connection between a duct and fire damper according to DW/145. The FFDM is a flanged breakaway joint with a plastic pad which will melt at 80°C, allowing the duct to break away from the damper and ensure the dampers integrity is maintained. Refer to FFDM – Technical specifications for options and insert requirements. Breakaway joint (supplied by others). Guidance for specification option: Insert requirements. Manufacturer guidanceBreakaway joints are a required accessory for the fire dampers. These joints are required on both sides of the damper. |
Country of product manufacture | Czechia |
Material | Steel |
Platform | Compatible | Version |
---|---|---|
- | 1 |
FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper
FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised - Fire Damper
FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper
FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper
FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper
FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper
FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper
FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper