NBS Source
I'm a manufacturer

Façade Louvred AOV Smoke Vent

Verified by manufacturer 5 months ago

Sertus Third party certifications:
  • Certificate of constancy of performance

    Certificate type

Smoke vent and air supply louvres used in natural smoke and heat exhaust ventilation systems (nSHEVS).

Jump to:
+44 (0) 1483 269999 Website

Application

  • For mounting in facades and end of corridors.
  • Particularly suited to apartment and commercial buildings.

Description

Façade Louvre Blade – Residential Glass (FLB-RG) smoke vents exhaust smoke and heat from a building allowing escape routes to be kept clear of smoke and are fully certified to BS EN 12101-2. They may also offer inlet air and comfort ventilation. They are available in a wide range of louvre glazing options and control systems. They are fitted with an anti-trapping actuator providing protection from injury and offer high resistance to weather and are therefore suited for use in exposed and high wind areas. They provide good security and do not create a fall hazard when open.

 

Optional:

  • Vertical frame connection detail for continuous vertical louvres for high atriums or feature glazing.
  • A wide range of glass to achieve specific Light Transmission (LT) and Solar Gain (g-value).
  • A range of aluminium cills are available to enable units to be installed in masonry facades and maintain weathering detail.


Features and benefits:

  • Fully certified to BS EN 12101-2.
  • Available in a wide range of sizes and blade options.
  • Opens to 85° within 60 seconds.
  • Consumes minimal energy during operation.
  • High resistance to weather and wind load.
  • When open is not a fall hazard.
  • Sound reduction with acoustic insulation up to 48 dB RW.
  • Impact resistant to DIN 18032-3.
  • Barrier load tested to BS 6180:2011.
  • Anti-trapping actuator provides protection from injury.

General information

Color

Other

Finish

Powder-coated

Material

Aluminium

Glass

Shape

Rectangle

Width

1000 mm

Bespoke

Height

2000 mm

Bespoke

Warranty description

Five year

Two year

Manufacturer guidance

Five years: Louvre unit.

Two years: Electrical actuator and opening mechanism.

Uniclass

Pr_70_65_04_56 Natural smoke and heat exhaust ventilatorsPrimary

CAWS

L10/47 Roof ventilators

L10/490 Roof ventilators

Specification data - Natural smoke and heat exhaust ventilators

Standard

To BS EN 12101-2.

Third-party certification

Certificate of constancy of performance.

Mounting

Wall-mounted.

Reliability classification

Re 1000 (10 000 + 1000).

Snow load classification

SL 0.

Low ambient temperature classification

T (-05).

Wind load classification

WL 1500–3000.

Resistance to heat classification

B300.

Arrangement

Louvred.

Dimensions

-

Width

-

Manufacturer guidance

Insert requirements or refer to a drawing or schedule.


Subject to the overall size of window and louvre blade heights the frame width can be manufactured from 350 mm to 2500 mm. For larger spans, there is a special centre mullion design.

Height

-

Manufacturer guidance

Insert requirements or refer to a drawing or schedule.


Minimum blade height of 200 mm and maximum blade height of 450 mm.

Controls

Linear actuator.

Initiation

24 V d.c. power open, power close.

Materials

-

Ventilator

-

Frame

Aluminium.

Manufacturer guidance

The frame sections are 40 mm wide and 77 mm deep, with mitre joints and are manufactured from thermally broken aluminium.

Louvres

Multi-blade aluminium.

Glazing

32 mm insulating glazing unit.

Guidance for specification option:

Toughened inner/ laminated outer double-glazed blades with argon-filled cavity and warm edge spacer.

Triple glazed.

Solid insulated blade.

Manufacturer guidance

Optional feature: A wide range of glass is available to achieve specific Light Transmission (LT) and Solar Gain (g-value); consult manufacturer for details.

Finish

Polyester powder-coated.

Principal components polyester powder-coated, solid blades mill finish.

Colour

-

Manufacturer guidance

Available in standard RAL colours, insert requirements.

Seals

Brush seals.

Guards

Anti-finger trapping motor.

Accessories

Thermally broken sill profile.

Glazing adaptor for facade glazing systems.

Impact resistance

To DIN 18032-3.

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

Certificate of constancy of performance

Certificate of constancy of performance

Certificate of Constancy of Performance – Façade Louvre Blade (FLB-RG)

Literature

Sertus FLB-RG Technical Data Sheet

Sertus FLB-RG Technical Data Sheet

Sertus FLB-RG Installation Guide

Sertus FLB-RG Installation Guide

Sertus FLB-RG Declaration of Performance

Sertus FLB-RG Declaration of Performance

Sertus FLB-RG Operation & Maintenance Manual

Sertus FLB-RG Operation & Maintenance Manual

Sertus FLB-RG Warranty

Sertus FLB-RG Warranty

Case studies

Sudbury House

Sudbury House

Dagenham Flats

Dagenham Flats

Similar products from Sertus

Façade Single Leaf AOV Smoke Vent

Façade Single Leaf AOV Smoke Vent

Roof Louvred AOV Smoke Vent

Roof Louvred AOV Smoke Vent

Roof Single Leaf AOV Smoke Vent

Roof Single Leaf AOV Smoke Vent