Extended Corridor System

Extended Corridor System

Third party certifications:
  • QA Certificate

    QA Certificate

    Certificate type

Colt International Ltd

Smoke and heat exhaust shaft ventilation system for means-of-escape corridors in residential buildings.

Jump to:
+44 (0)23 9245 1111 www.coltinfo.co.uk
Description

Approved Document B (Fire safety) recommends that where there is a dead-end corridor, the travel distance from the dwelling door to the staircase is limited to 7.5 metres. The Extended Corridor System allows safe escape conditions to be maintained in the corridor, even when the travel distance is extended by a factor of 2 or 3 in one direction. It is designed for both evacuation and fire-fighting. The system is generally unaffected by external wind pressure.

The system comprises a supply and extract system with shafts at each end of the corridor. Vertical builders' ducts are required at each end of the corridor which will supply fresh air and provide smoke extraction to fans mounted at roof level, providing a smoke dilution system to the fire floor. The ductwork is nominally only 0.6 m² in cross sectional area, enabling a much reduced footprint compared to alternative solutions.

The Extended Corridor System is a LABC Registered System because of its superior performance as proven by CFD and full scale physical testing, witnessed and approved by independent consultants including the London Fire and Emergency Planning Authority.

Features and benefits:

  • Space saving - The Extended Corridor System requires a shaft with a cross sectional area which can be as small as only 0.6 m² compared with 3 m² for the BRE shaft or 1.5 m² for a natural residential (ADB) shaft. This represents up to 80% reduction in the floor space required.
  • Enhanced performance - The Extended Corridor System can perform better than a BRE Shaft since it extracts at a defined rate - this means that it is unaffected by external wind pressures. It is also less susceptible to obstructions to the airflow within the duct. Its design has been proven by extensive CFD analysis and by empirical tests.

General information
Specification data - Pressure differential systems

Product Reference

Extended Corridor System

Components

Controls

Defender F flap ventilator

To each corridor.

Doorman

Motorised smoke damper and grille

Seefire ducted termination

Seefire ventilator

Smoke extract fan

Standard product features

System components:

  • Extract – duty and standby extract fans rated at 300ºC for one hour.
  • If inlet is by using a mechanical shaft, then duty and standby fans, ambient rated.
  • Either a motorised smoke damper and grille or a Defender F flap ventilator to each corridor (minimum E30S rated).
  • Main control panel plus mimic panel for fire service use.
  • MCC/Fan starter panel.
  • Smoke detector in the corridor at each level.

Literature
Third party certifications
  • LABC Approved
  • RD Certificate Number: EWW78A
Similar products from Colt International Ltd