Fire barrier for use in partitioning, ducting, door and ceiling applications.
DURASTEEL® systems have been used successfully for many years, including rail and metro projects, military developments and in commercial, pharmaceutical and petrochemical facilities.
Fire barrier for use in partitioning, ducting, door and ceiling applications.
DURASTEEL® has been developed and supported through rigorous testing for use in partitioning, ducting, door and ceiling applications, with a wide range of specifications available.
Features and benefits:
Construction:
Application:
DURASTEEL® systems have been used successfully for many years, including rail and metro projects, military developments and in commercial, pharmaceutical and petrochemical facilities.
Features | Combines lightness, strength, impact resistance and durability with exceptional fire resistance; systems remain resistant to firefighters’ hoses, leaving them capable of performing their original function even in the aftermath of a fire |
Finish | Studded |
Material | Steel (anchors) |
Shape | Vertical and horizontal channels Rectangular |
Size | Overall width: 89.5, 118 or 137 mm, dependent on insulation specified. Channels up to 6 m are 80 x 60 x 3 mm |
Uniclass 2015 | |
CAWS | K10/125 Metal stud partition system K10/30 Metal stud |
Product Reference | Durasteel Fire Barrier |
Framing | Manufacturer's standardPerimeter channels fastened to surrounding construction with M10 or M12 all-steel expanding anchors, vertical channels at maximum 1200 mm centres. Horizontal and vertical channel members either welded together or joined with steel angle cleats. |
Insulation | No insulationIntegrity only. Estimated sound reduction: 33 dB. Overall width: 89.5 mm. 60 minutes' insulationEstimated sound reduction: 47 dB. Overall width: 118 mm. 120 minutes' insulationEstimated sound reduction: 47 dB. Overall width: 118 mm. 240 minutes' insulationEstimated sound reduction: 50 dB. Overall width: 137 mm. |
Cavity fire barriers | Dependent on insulation specifiedFire barriers have 240 minutes' integrity. All fire barriers are resistant to fire attack from either face. |
Fasteners | Manufacturer's standardFor 120/ 240 minutes' insulation: M10 steel nuts and bolts. |
Standard product features | Features: Combines lightness, strength, impact resistance and durability with exceptional fire resistance; systems remain resistant to firefighters’ hoses, leaving them capable of performing their original function even in the aftermath of a fire. Finish: Studded. Material: Steel (anchors). Shape: Vertical and horizontal channels. Size: Overall width: 89.5, 118 or 137 mm, dependent on insulation specified. Channels up to 6 m are 80 x 60 x 3 mm. Shape: Rectangular. |