NBS Source
I'm a manufacturer
Compare variants

Durasteel Composite Barrier System

Verified by manufacturer 2 months ago

Durasteel Composite Barrier System - 120 minutes' insulation

Promat UK Variant:
Third party certifications:
  • Certifire Certificate

    Certifire Certificate

    Certificate type

Fireproof boards for use with internal walling.

Jump to:
0800 145 6033 Website

Application

For use with internal walling. DURASTEEL® systems have been used successfully for many years, including rail and metro projects, military developments and in commercial, pharmaceutical and petrochemical facilities.

Description

Fireproof boards for use with internal walling.


Features and benefits:

  • Combine lightness, strength, impact resistance and durability with exceptional fire resistance.
  • Systems remain resistant to firefighters’ hoses, leaving them capable of performing their original function even in the aftermath of a fire.
  • Gap in the Durasteel and Promatect 250 board facing is covered with a Durasteel and Promatect 250 board cover panel.

General information

Finish

Galvanized

Material

Steel

Shape

Rectangle

Guidance for specification option:

Vertical and horizontal channel members.

Uniclass

Ss_25_10_30_70 Rigid sheet partition systemsPrimary

CAWS

K10/125 Metal stud partition system

K10/30 Metal stud

K40/10 Unit/ modular suspended ceilings

Specification data - Rigid sheet partition systems

Framing

Manufacturer's standard.

Guidance for specification option:

For internal surfaces PROMATECT® 250 boards fixed at 600 mm centres. For horizontal jointing boards are fitted with an internal 100 x 15 mm PROMATECT® 250 cover strip fixed at both sides of the joint at 250 mm nominal centres. Vertical jointing is to coincide with studs and DURASTEEL® sheet to be fixed to PROMATECT® 250 board at 250 mm centres.

Cavity fire barriers

120 minutes' insulation.

Fasteners

Manufacturer's standard.

Guidance for specification option:

Tapping Tek screws at 250 mm nominal centres. M10 steel nuts and bolts used to fasten vertical channels.