NBS Source
I'm a manufacturer
Compare variants

CR60 - Circular EIS Fire Damper (max Ø 315mm) - Fire Damper

Verified by manufacturer 7 months ago

CR60-L500 fire damper

Rf-Technologies Variant:
Third party certifications:
  • Classification report acc. to EN 13501-3

    Certificate type

  • DoP

    DoP

    Certificate type

  • UK Conformity Assessed (UKCA)

    UK Conformity Assessed (UKCA)

    Certificate type

Circular EIS fire damper with a fire resistance of 30, 60 or 90 minutes depending on the installation type, both for motorized and non-motorized applications. (previously known as FD and FSD / MFSD)

Jump to:
+44 7939316006 Website

Application

Circular EIS fire damper with a fire resistance of 30, 60 or 90 minutes depending on the installation type, both for motorized and non-motorized applications.

(previously known as FD and FSD / MFSD)


CR60 Certified installations and sealing methods:

  • In wall & floor:
  • rigid wall & floor.
  • flexible wall.
  • asymmetrical flexible wall (shaft wall).
  • Remote of wall.
  • For full details: CR60 Declaration of Performance (DoP) - see associated content.


CR60 Fields of application:

  • Passive fire protection.
  • Ventilation systems.


CR60 Building applications:

  • Industrial, commercial & residential buildings.
  • Hospitals and care houses.
  • Data centres and battery plants.
  • Detention institutes.
  • Universities, colleges and schools.

Description

Circular EIS fire damper with a fire resistance of 30, 60 or 90 minutes depending on the installation type, both for motorized and non-motorized applications.

(previously known as FD and FSD / MFSD)


CR60 Distinct Product Features (incl. specifications)

  • CE certified against EN 1366-2 and EN 15650.
  • UKCA certified.
  • i <-> o certified.
  • Air-tightness class C against EN 1751.
  • Up to 500 Pa pressure level (standard 300 Pa).
  • Hygiene certified.
  • Swedish BVD and SundaHus rating in place.
  • Minimal distance certified against EN-1366-2.
  • Single, thin insulated damper blade.
  • No mechanics inside the damper body.
  • Fusible link aligned with the open damper blade.
  • 72°C fusible link temperature threshold.
  • Insulated damper body (to meet I criteria).
  • Support lugs aligned to DW145 guidance.
  • Designed for use with Belimo motor range (24/ 230 V).
  • Designed for use with ONE motor range (24/ 230 V).
  • Designed for use with ONE-X and ZENiX.
  • Note for clarification:
  • ONE is a motor by Rf-Technologies.
  • ONE-X is motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies.


CR60 User Benefits:

  • Minimal impact on building space requirements thanks to the minimal distance CE certification and the compact damper and mechanics design
  • down to 30 mm vs. structure or between dampers (instead of 200 mm standard CE).
  • Minimal pressure loss in the damper body and ventilation system
  • ultimately leading to lower system investments and energy consumption.
  • Minimal acoustic / noise impact.
  • Lowest standby power consumption in the market when using the ONE motor.
  • Easy installation and maintenance (compared to traditional UK type fire dampers).


CR60 range:

  • Diameter (mm) 100 to 315.
  • Tunnel casing (mm) 345 or 500.


Notes:

  • For information about the different types of installation and sealing methods please consult the CR60 Product application field and or the CR60 Declaration of Performance (DoP).
  • For a 120 minutes requirement please consult the CR120.


Relevant Links:


General information

Color

White

Silver

Finish

Galvanized

Guidance for specification option:

Standard body (casing) (steel)

Epoxy

Guidance for specification option:

Inner body & blade

  • Optional at order
  • Resistance against "aggressive" fluids and gases

Material

Steel

Guidance for specification option:

Casing.

Shape

Circle

Length

345 mm

Guidance for specification option:

Standard models.

500 mm

Guidance for specification option:

L500 models.

Width

100 mm

125 mm

150 mm

Guidance for specification option:

Not available for CR60-1S models.

160 mm

180 mm

Guidance for specification option:

Not available for CR60-1S models.

Show more

Manufacturer guidance

Diameter.

Height

100 mm

125 mm

150 mm

Guidance for specification option:

Not available for CR60-1S models.

160 mm

180 mm

Guidance for specification option:

Not available for CR60-1S models.

Show more

Manufacturer guidance

Diameter.

Warranty description

One year

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire/ smoke

Specification data - Fire and smoke dampers

Standard

-

Fire dampers

To EN 15650:2010.

Test

To EN 1366-2.

Guidance for specification option:

Up to 500 Pa.

Classification

To EN 13501-3.

Arrangement

Single-blade.

Classification

Guidance for specification option:

Up to EI90 dependent upon installation requirements; consult manufacturer and insert details.

Material

Galvanized steel.

Guidance for specification option:

Tunnel casing.

Consult manufacturer for details of other components.

Accessories

Inspection opening in tunnel body.

Limit switch (open/closed).

Guidance for specification option:

To suit specified thermal release mechanism.

None.

Fusible links

-

Fusing temperature

72°C.

Dimensions

100 mm diameter, 500 mm long.

125 mm diameter, 500 mm long.

150 mm diameter, 500 mm long.

160 mm diameter, 500 mm long.

180 mm diameter, 500 mm long.

Show more

Pressure loss

Guidance for specification option:

Insert details, dependent on required damper size and air flow/air speed; consult manufacturer's technical literature for details.

Air tightness

Class C.

Guidance for specification option:

To EN 1751.

Thermal release mechanism

Actuator - ONE T 24 V.

Actuator - ONE T 230 V.

Actuator - ONE-X 24 V.

Guidance for specification option:

Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies.

Actuator - ONE-X 230 V.

Guidance for specification option:

Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies.

Actuator - Belimo 24 V.

Show more

Integral accessories

Tunnel casing extension.

Guidance for specification option:

  • Extension at the wall side to facilitate the connection to the duct when the supporting  construction is thicker than 100 mm.
  • This variant also ensures that the damper blade doesn’t exceed the casing at the wall side (up to a height of 550 mm), which allows to connect a grill or a bend directly on the damper flange or to use a circular connection.

Third-party certification

CE marked BCCA-0749-CPR-BC1-606-0464-15650.02-2517.
UKCA marked 2822-UKCA-CPR-0055.
NF537 marked 18.16.
VKF/ AEAI certificate 26815.
Hy hygiene certificate W-336769-20-Zd.
RISE certificate SC0648-15.

Sustainability data

Country of product manufacture

Belgium

Third party certifications

Classification report acc. to EN 13501-3

Classification report acc. to EN 13501-3

CR60 Classification Report

DoP

DoP

CR60 Declaration of Performance (DoP)

UK Conformity Assessed (UKCA)

UK Conformity Assessed (UKCA)

CR60 UKCA Certificate

Literature

CR60 DW145 compliant installation guide - plasterboard wall

CR60 DW145 compliant installation guide - plasterboard wall

CR60 Technical Product Documentation

CR60 Technical Product Documentation

CR60 DW145 compliant installation guide - rigid wall

CR60 DW145 compliant installation guide - rigid wall

CR60 DW145 compliant installation guide - floor/ceiling

CR60 DW145 compliant installation guide - floor/ceiling

Case studies

CR60 and ONE Reference Project - Resecentrum Göteborg, Sweden

CR60 and ONE Reference Project - Resecentrum Göteborg, Sweden