Non-Addressable Zone Monitor - M210E-CZ
Conventional zone monitor module allows a zone of non-addressable detectors to communicate with a Morley IAS analogue addressable system.
Conventional zone monitor modules that allow conventional zones to be integrated into intelligent systems for flexibility in system design and retrofit applications.
The M210E-CZ and M210EA-CZ/CZR conventional zone monitor modules provide a means of connecting zones of non-addressable detectors to a Morley-IAS analogue addressable fire alarm system. These modules allow conventional zones to be integrated into intelligent systems for flexibility in system design and retrofit applications.
The M210E-CZR is supplied with a built-in resistor, making it particularly suitable for use in hazardous areas requiring intrinsically safe (IS) equipment. The M210EA-CZ allows the conventional zone to be powered either from the analogue loop or from an external power supply. When powered externally, the zone and supply are fully isolated from the loop to maintain system integrity. Fault conditions, including open circuits, short circuits, or activation of the external fault input, are transmitted directly to the control panel.
Features and benefits:
Color | White |
Finish | Smooth |
Material | Plastic |
Shape | Square |
Length | 22 mm |
Width | 93 mm |
Height | 99 mm |
Uniclass | |
CAWS | S92/420 Alarm devices W90/120 Fire detection and alarm systems in domestic premises W90/125 Fire detection and alarm systems in non-domestic premises |
SKU Code | M210E-CZ |
Classification data | |
Accessories | M200E-SMB - surface mounting box. |
Dimensions | 99 x 93 x 22 mm. Manufacturer guidanceH x W x D. |
Weight | 0.118 kg. |
Current | Max standby current external supply: 120 uA @ 24 V. Max standby current: 1.3 mA @ 24 V. |
Power supply | 18–32 V. Manufacturer guidanceExternal power supply voltage. |
Electric resistance | 50 Ω. Manufacturer guidanceMaximum series resistance. |
Operating temperature range | -20°C to +60°C. |
Humidity | 5–95% relative humidity (non-condensing). |
Ingress protection | IP44. Guidance for specification option: Mounted in M200E-SMB. |
Material | Plastic |