NBS Source
I'm a manufacturer
Compare variants

AXS 140

Verified by manufacturer 4 days ago

1000 x 1250 mm ventilator, aluminium lid

Colt International Ltd Variant:

AXS 140 is a combined AOV smoke ventilator and roof access hatch providing appropriate free area in accordance with Approved Document B, Appendix C.

Jump to:
+44 (0)23 9245 1111 Website

Application

Combined AOV smoke ventilator and roof access hatch designed providing either 1.0 or 1.5 m² measured free area in accordance with Approved Document B, Appendix C.

Suitable for use as a staircase ventilator or roof mounted lobby/ corridor ventilator and to provide external roof access.

Description

AXS 140 is a combined AOV smoke ventilator and roof access hatch providing minimums of either 1 m2 or 1.5 m2 free area in accordance with Approved Document B.

It is suitable for use as a staircase ventilator or roof mounted lobby/corridor ventilator to provide external roof access. It has been tested to and is in compliance with BS EN 12101-2 and is CE marked. It is manufactured under the ISO 9001 quality and ISO 14001 environmental management standards.

Product Highlights:

  • Dual-purpose: natural smoke ventilator and roof access hatch (1.0 or 1.5 m² free area).
  • Certified to BS EN 12101-2, CE marked for life safety and ventilation compliance.
  • Opens to 140° for rapid smoke clearance and safe, easy roof access.
  • Durable aluminium and stainless steel build with airtight EPDM sealing.
  • Thermal U‑value down to 1.3 W/m²K and acoustic insulation up to 29 dB R’w.
  • Polycarbonate daylighting option available

Product Technical Information

Dimensions / size range:

  • (SM) 1250 x 1000 (throat dimensions).
  • (LG) 1250 x 1500 (throat dimensions).

Flap options:

  • Thermally broken aluminium frame and insulated aluminium panel.
  • Thermally broken aluminium frame and polycarbonate panel.

Fits tightly to frame with continuous EPDM seals for excellent airtightness. Opens to 140⁰ from the horizontal.

Colours/ finishes options:

  • Mill finish.
  • Polyester powder painted to a RAL colour, standard 40 µm.

Fixing options:

Fixing flange for curb. Installation angle must be at 0° (horizontal).

General information

Color

Silver

Guidance for specification option:

Standard (mill finish).

Other

Guidance for specification option:

RAL colour.

Finish

Powder-coated

Guidance for specification option:

Polyester powder-coated.

Material

Aluminium

Stainless steel

EPDM

Shape

Rectangle

Length

1350 mm

1600 mm

Width

1600 mm

1850 mm

Height

398 mm

Uniclass

Pr_70_65_04_56 Natural smoke and heat exhaust ventilatorsPrimary

CAWS

L10/45 Rooflights

L10/460 Rooflights

L10/47 Roof ventilators

L10/490 Roof ventilators

Product range

Natural flap ventilators

Specification data - Natural smoke and heat exhaust ventilators

Classification data

Opening type

B.

Mounting

Roof-mounted.

Aerodynamic free area

1.0 m².

Reliability classification

Re 50.

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.


Watertightness: Rain defence tested to 75 m/h (at 13 m/s).

Sound insulation: <29 dB Rw.

Snow load classification

250 N/m².

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.

Low ambient temperature classification

T (-05).

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.

Wind load classification

WL 1500.

Guidance for specification option:

1500 N/m².

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.


Air permeability (to BS EN 12207): Class 4.

Resistance to heat classification

B300.

Guidance for specification option:

Resistance to fire (to BS EN 13501-1): E.

Manufacturer guidance

Performance attribute; following tests to EN 12101-2:2003 (standard for smoke and heat exhaust ventilators). The exact performance attribute will depend on the chosen size, controls, and flap type.

Arrangement

Insulated aluminium panel.
Polycarbonate panel.

Dimensions

-

Length

1600 mm.

Guidance for specification option:

Overall length.

Width

1350 mm.

Guidance for specification option:

Overall width.

Height

398 mm.

Controls

24 V d.c. linear actuator (drive in/ drive out).

Guidance for specification option:

Motor: 2.6 A; 62.4 W; 1550 N.

Manufacturer guidance

Mounted on a pivoting carriage capable of opening the lid to the fire position of 140° from the horizontal within 60 seconds and of re-closing it.

Materials

-

Ventilator

-

Frame

Aluminium.

Guidance for specification option:

Thermally broken aluminium frame with continuous seals for excellent airtightness. Opens to 140° from the horizontal.

Glazing

As arrangement.

Finish

Mill finish.
Polyester powder-coated.

Guidance for specification option:

Insert colour requirements below.

Standard 40 µm.

Colour

Silver.

Guidance for specification option:

Standard for mill finish.

RAL.

Guidance for specification option:

Many colour options available; consult manufacturer for details and insert requirements.

Integral upstands

-

Material

Manufacturer's standard.

Guidance for specification option:

Thermally broken, 40 mm-thick welded insulated and thermally broken aluminium. EN AW-6063 T6 (extrusion) and EN AW-3005 H14 (sheet) aluminium alloy.

Finish

As ventilator.
Mill finish.
Polyester powder-coated.

Guidance for specification option:

Insert colour requirements below.

Standard 40 µm.

Colour

As ventilator.
Silver.

Guidance for specification option:

Standard for mill finish.

RAL.

Guidance for specification option:

Many colour options available; consult manufacturer for details and insert requirements.

Seals

EPDM profiles.

Guidance for specification option:

Keeps air leakage down to a minimum.

U-value

Up to 1.3 W/m²K.

Fixing

Fixing flange for curb.

Guidance for specification option:

Installation angle must be at 0° (horizontal).

Sustainability data

Material

Aluminium
Stainless steel
EPDM

Literature

AXS 140

AXS 140

Similar products from Colt International Ltd

Apollo ATI 

Apollo ATI 

Coltlite

Coltlite

ECO / EN-Seefire (ECO)

ECO / EN-Seefire (ECO)

Firelight Duo 

Firelight Duo 

Weatherlite 

Weatherlite