Verified by manufacturer 4 days ago
A9L8F461 / Isobar P
Type 2+3 SPD’s from Acti9 Isobar P and KQ load centre product range.
The iPRD range shall be suitable for installation on two types of fishbone type distribution boards according to the international standard EN 60715 and DIN43880 1988.
The SPD shall be able to fit on Acti9 Isobar-P distribution boards, or into one Acti9 KQ load centres.
The iPRD range shall be a surge protection device:
The iPRD range shall include products with added functions to offer simplification of installation inside the cabinet and remote supervision of the product end of life.
- End of life Remote supervision:
General rules for SPD :
Products should conform to following Additional Related Standards – standards not necessarily directly applicable to the product itself but which need to be considered during the development program either in part or in total includes:
CE and UKCA marked. Meets the requirements of LV Directives: 2014/35/EU.
Color | White |
Material | Plastic |
Shape | Rectangle |
Uniclass |
Classification data | |
Standard | To BS EN 61643-11, Type 2 + Type 3. |
Operating voltage and frequency (nominal) | 230 V. |
Number of poles | 3PN. |
Maximum continuous operating voltage (Uc) | 340V / 260V. |
Mode of protection | L/N protection: MOV technology. N/PE protection: GDT technology. |
Nominal discharge current (In) | 20 kA per mode. |
Maximum discharge current 8/20 µs (Imax) | 40 kA per mode. |
Minimum short circuit current rating (Isccr) | 25 kA stand alone and installed in Fishbone panelboard (tested at 50 kA in lab not a scope of VDE CB). |
Voltage protection level (Up) | 1500 V. |
Open circuit voltage (Uoc) | 6 kV. |
Protection status indicators | Green indicating full protection status. Red indicating no protection – failure of device. |
Remote monitoring | Required (Available with Acti9). None. Guidance for specification option: Not available with iKQ. |
Ingress protection (minimum) | To BS EN 60529, IP40 (device in panel board). IP 20 (Device wired and cartridge removed). |
Mounting method | The SPD shall be suitable for installation on DIN rail according to the international standard EN 60715. Both designed exclusively to be mounted on Acti9 Isobar P and/or KQ Loadcentre boards. |
Material | Plastic |
Expected Life | 20 year |