NBS Source
I'm a manufacturer

1 Loop Analogue Addressable Fire Control Panel

Verified by manufacturer 4 months ago

Hochiki Europe (UK) Ltd Third party certifications:
  • Certificate of Approval

    Certificate of Approval

    Certificate type

  • ISO 9001 Quality Management

    Certificate type

Single loop fire control panel which supports Hochiki ESP loop drivers, which are all capable of providing up to 400 milliamps of loop current for the most demanding applications.

Jump to:
+44 (0)1634 266566 Website

Application

Fire detection systems.

Description

The HFP AP-AS is a powerful and versatile single loop Analogue Addressable Fire Control Panel. HFP AP-AS supports Hochiki ESP loop drivers, which are all capable of providing up to 400 milliamps of loop current for the most demanding applications.


An integral 3 Amp power supply and temperature compensated battery charger provides ample power for the two, 1 Amp rated standard sounder outputs, loop powered sounders and other devices. HFP AP-AS is also available as a HFP AP-ASL version offering a very cost effective solution for smaller standalone installations requiring only one detection loop.


The HFP AP-ASL version does not support the following: Second loop, Printer output, Networking and connection of I/O boards or the HFP AP-CRL repeater.


Feature and benefits:

  • 16 zonal LED indicators.
  • 2 programmable sounder circuits.
  • 5 programmable inputs.
  • 3 programmable relays.
  • 3A power supply.
  • Large graphic display.
  • Certified to EN 54-2/ EN 54-4.
  • Up to 512 additional programmable I/O via HFP I/O modules.
  • Powerful, network wide cause and effects.
  • Sensitivity adjustment and Drift Compensation.
  • Can be networked with HFP control panels.
  • Compatible with HFP and HFP AP-CRL repeaters.
  • Stores 500 last events in event log.
  • Dial up modem connection available.
  • Compact, stylish enclosure.
  • Installer friendly, removable equipment chassis.
  • Different language and character set variants available.
  • Fully EN 54-2 and EN 54-4 compliant improved front loading Printer option.
  • Keyswitch
  • Mains supply fuse 1.6A 250 V.
  • Power supply DC rating 24V 3 Amps.
  • Aux 24V supply Fused at 500 milliamps.
  • Maximum Battery size 9Ah 12V (2 per panel) (non-networked).
  • Fault contact rating 30V DC1 Amp.
  • Fire contact rating 30V DC1 Amp.
  • Alarm contact rating 30V DC1 Amp.
  • Sounder output rating Fused at 1 Amp each.
  • Detection loop 400 milliamp output.

General information

Color

Grey

Finish

Powder-coated

Material

Carbon steel

Shape

Rectangle

Length

90 mm

Guidance for specification option:

Depth

Width

385 mm

Height

310 mm

Warranty description

Three year

Uniclass

Pr_75_80_30_29 Fire alarm panelsPrimary

CAWS

W90/120 Fire detection and alarm systems in domestic premises

W90/125 Fire detection and alarm systems in non-domestic premises

Specification data - Fire alarm panels

Standard

To BS EN 54-2 and BS EN 54-4.

Standby power supply

-

Standard

To BS EN 54-4.

Main display

Eight lines of 40 characters graphic LCD.

Zone indication

Individual LED status indicators.

Installed capacity

16-zone.

Monitored sounder circuits (minimum)

Two.

Printer

Output to separate printer.

Enclosure

-

Ingress protection (minimum)

IP30.

Material

1.2 mm carbon sheet steel.

Finish

Powder-coated.

Colour

Grey.

Mounting

Surface.

Voltage

110 V a.c.

230 V a.c.

Guidance for specification option:

Standard.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Carbon steel

Manufacturing plant location

Expected Life

Ten year

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

Certificate of Approval

Certificate of Approval

BSI Kitemark Licence | EN54-2 and EN54-4 | Devices: HFP AP

ISO 9001 Quality Management

ISO 9001 Quality Management

Certificate of Management System Registration - ISO 9001:2015 - Quality Management Systems

Literature

HFP AP-AS Analogue Addressable 1-2 Loop Control Panels

HFP AP-AS Analogue Addressable 1-2 Loop Control Panels

Hochiki BS 5839 Guide

Hochiki BS 5839 Guide

Hochiki Corporate Overview

Hochiki Corporate Overview

Hochiki Project Portfolio

Hochiki Project Portfolio

Hochiki Ekho (Hybrid Wireless) Range Overview

Hochiki Ekho (Hybrid Wireless) Range Overview

Hochiki - ESP - Intelligent Fire Detection - Range Overview

Hochiki - ESP - Intelligent Fire Detection - Range Overview

Hochiki - Latitude - Fire Control Panel - Range Overview

Hochiki - Latitude - Fire Control Panel - Range Overview

Hochiki - SIL2 Capable - Range Overview

Hochiki - SIL2 Capable - Range Overview

Hochiki - Marine - Approved Fire Detection - Range Overview

Hochiki - Marine - Approved Fire Detection - Range Overview

Hochiki - VADs - Visual Alarm Devices - Range Overview

Hochiki - VADs - Visual Alarm Devices - Range Overview

Similar products from Hochiki Europe (UK) Ltd

2 Loop Analogue Addressable Fire Control Panel

2 Loop Analogue Addressable Fire Control Panel

HFP Latitude 2–8 Loop Control Panel (5.25A PSU) With Key Switch, 0–144 Zone LED’s

HFP Latitude 2–8 Loop Control Panel (5.25A PSU) With Key Switch, 0–144 Zone LED’s

HFP Latitude 2–8 Loop Deep Enclosure Control Panel (10.25A PSU) With Key Switch, 0–144 Zone LED’s

HFP Latitude 2–8 Loop Deep Enclosure Control Panel (10.25A PSU) With Key Switch, 0–144 Zone LED’s