NBS Source
I'm a manufacturer

Compare variants

Fire Curtain - Vertical Flameshield 8524 (S) Fire and Smoke Curtain - Fire and Smoke Curtain
Fire Curtain - Vertical Flameshield 8524 (S) Fire and Smoke Curtain - Fire and Smoke Curtain
Fire Curtain - Vertical Flameshield 8524 (S) Fire and Smoke Curtain - Fire and Smoke Curtain

Verified 18 days ago

A1S Group

Verified 18 days ago

A1S Group

Verified 18 days ago

A1S Group
Summary
An automatic vertical fire curtain barrier that has 120 minutes integrity and 85 minutes radiation, tested to BS EN 1634-1 and BS EN 1634-3 in accordance with BS 8524-1.
Product certifications
Digital objects
-
-
Color
Other
-
-
Finish
Powder-coated
-
-
Material
Carbon steel
-
-
Shape
Rectangle
-
-
Length
Bespoke
-
-
Width
10000 mm
-
-
Height
10000 mm
-
-
Warranty description
One year
-
-

Specification

Standards
To BS 8524, BS EN 12605, BS EN 14600, BS EN 13501, BS EN 16034, BS EN 1634 -1 and -3 and BS 476.
-
-
Barrier assemblies
To BS 8524-1, BS EN 1634-1 and BS 1634-3.
-
-
Test standards
Vertical, horizontal and angled to BS EN 1634-1.
-
-
Third-party certification
IFCC 1542 and IFCC 3425. Warrington Fire Report 340986.
-
-
Performance
-
-
-
Pressure and impact
Tested to BS 5234-1 (Clause 5.2 BS 8524-1) Warrington Test number WIL 403113 Issue 3.
-
-
Durability class
C1.
-
-
Smoke containment
No smoke seals.
-
-
Fire resistance
60 minutes., 120 minutes integrity classified to EW60.
-
-
Reaction to fire
To BS 476-6 and BS 476-7.
-
-
Deployment
Immediate deployment from receipt of alarm signal. Split and delay drop facilities with timed hold.
-
-
Activation
Specialist panel with internal battery back up and modified motor. Activation on receipt of relevant alarm signal.
-
-
Accessories
Partial Drop., Emergency Retract., BMS Interface., Single Photo Cell., Audio / Visual / Spoken Warning Unit., Egress switches., Access switches.
-
-

Additional properties

Radiation
85 minutes at <15 kW/m². 124 minutes at <20 kW/m².
-
-
Fabric
Fire curtains are formed from a fire rated fabric 0.54 mm thick stainless steel wire reinforced, with a specially formulated aluminum pigmented and fire retardant polymer which provides a heat reflecting surface as well as other properties for smoke and fire.
-
-
Barrel
Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards.
-
-

Sustainability data

Material
Carbon steel
-
-