NBS Source
I'm a manufacturer

Compare variants

Eco Active MVHR Unit - Heat Recovery Systems
Eco Active MVHR Unit - Heat Recovery Systems
Eco Active MVHR Unit - Heat Recovery Systems

Verified 7 months ago

GDL Air Systems Ltd

Verified 7 months ago

GDL Air Systems Ltd

Verified 7 months ago

GDL Air Systems Ltd
Summary
Heat recovery systems.
-
-
Application

Suitable for education and residential applications.

-
-
Description

Situated within a high-level void or exposed, giving winter and summer ventilation and also summer night time purging to each room. These units can also be externally roof mounted.


Each unit contains a heat exchanger with a minimum efficiency of 74%, giving a minimum supply air temperature of 17°C. Units also have low energy EC supply and extract fans handling volumes up to 1.0 m3/s.


Each unit is controlled via a CO2/ temperature room sensor and intelligent controller to give the correct ventilation at all times.


Features and benefits:

  • Ensures air quality and temperature remain within Department of Education guidelines.
  • Easy to use room controllers.
  • Summer boost and night purge mode.
  • Low maintenance with a range of colours available.
  • Low noise - Independently tested to BS EN ISO 3744:2010 meeting BB93 criteria and verified for use within educational establishments.
  • ErP 2018 compliant.
-
-
Color
Silver, Other
-
-
Finish
Galvanized, Powder-coated
-
-
Material
Steel, Aluminium
-
-
Shape
Rectangle
-
-
Length
1450 mm, 1800 mm, 2200 mm, 2450 mm
-
-
Width
1000 mm, 1200 mm, 1350 mm, 1550 mm, 1850 mm
-
-
Height
330 mm, 450 mm, 520 mm, 560 mm, 610 mm, 750 mm
-
-
SKU Code
EcoActive 100 HRU, EcoActive 200 HRU, EcoActive 300 HRU, EcoActive 400 HRU, EcoActive 500 HRU, EcoActive 600 HRU, EcoActive 700 HRU, EcoActive 800 HRU, EcoActive 900 HRU, EcoActive 1000 HRU, EcoActive 100 SB, EcoActive 200 SB, EcoActive 300 SB, EcoActive 400 SB, EcoActive 500 SB, EcoActive 600 SB, EcoActive 700 SB
-
-

Specification

Standard
To BS EN 13053.
-
-
Duty
-
-
-
Air volume
-
-
-
Supply
0.2 m³/s.
-
-
Extract
0.2 m³/s.
-
-
External resistance
250 Pa.
-
-
Sound power level
70 dB.
-
-
Environment
External., Internal.
-
-
Casing construction
-
-
-
Material
Galvanized sheet steel.
-
-
Finish
Self-finish., Polyester powder-coated.
-
-
Method of support
Suspended with M10 threaded rod either fixed through the pre-drilled holes within the corner sections or welded lugs.
-
-
Components
-
-
-
Dampers
-
-
-
Purpose
Bypass damper.
-
-
Filters
G4 panel air filters.
-
-
Heaters
-
-
-
Pre-heaters
-
-
-
Re-heaters
-
-
-
Cooling coils
-
-
-
Heat recovery
-
-
-
Heat recovery equipment
Plate heat exchanger - ERI Corporation PCF-I-3-95-280-T-BR-110-B-SM-HO.
-
-
Supply fan
-
-
-
Fan type
Centrifugal fans - GR20V-4IP.Z8.VR.
-
-
Extract fan
-
-
-
Fan type
Centrifugal fans - GR20V-4IP.Z8.VR.
-
-
Attenuators
Not required., EcoActive 100., EcoActive 200., EcoActive 300., EcoActive 400.
-
-
Accessories
Not required., Room sensor - CO₂ and temperature., Speed control.
-
-

Additional properties

Integral accessories
Access panel, side (removable panels on quarter turn cam locks and plastic handles).
Fresh air sensor, spigot side.
-
-
Leakage
To EN 16798-3.
-
-
Building Management System (BMS) connection
Modbus.
-
-
Flow rate
160 L/s., 200 L/s.
-
-
Support frame
Extruded aluminium to BS 1474 - 30 x 30 mm pentapost box section.
-
-
Mullions
Extruded aluminium to BS 1474 – 30 mm mullion joint.
-
-
Controls
Siemens Climatix Controllers, interface units, wall-mounted sensors and room operator units.
-
-
Dimensions
1450 x 1200 x 450 mm.
-
-
Unit weight
195 kg.
-
-

Sustainability data

Country of product manufacture
United Kingdom
-
-