Verified by manufacturer 2 months ago
EcoActive 100 HRU
Heat recovery systems.
Suitable for education and residential applications.
Situated within a high-level void or exposed, giving winter and summer ventilation and also summer night time purging to each room. These units can also be externally roof mounted.
Each unit contains a heat exchanger with a minimum efficiency of 74%, giving a minimum supply air temperature of 17°C. Units also have low energy EC supply and extract fans handling volumes up to 1.0 m3/s.
Each unit is controlled via a CO2/ temperature room sensor and intelligent controller to give the correct ventilation at all times.
Features and benefits:
Color | Silver Other |
Finish | Galvanized Powder-coated |
Material | Steel Aluminium |
Shape | Rectangle |
Length | 1450 mm 1800 mm 2200 mm 2450 mm |
Width | 1000 mm 1200 mm 1350 mm 1550 mm 1850 mm |
Height | 330 mm 450 mm 520 mm 560 mm 610 mm |
Uniclass |
SKU Code | EcoActive 100 HRU, EcoActive 200 HRU, EcoActive 300 HRU, EcoActive 400 HRU, EcoActive 500 HRU, EcoActive 600 HRU, EcoActive 700 HRU, EcoActive 800 HRU, EcoActive 900 HRU, EcoActive 1000 HRU, EcoActive 100 SB, EcoActive 200 SB, EcoActive 300 SB, EcoActive 400 SB, EcoActive 500 SB, EcoActive 600 SB, EcoActive 700 SB |
Standard | To BS EN 13053. |
Duty | |
Air volume | |
Supply | 0.1 m³/s. |
Extract | 0.1 m³/s. |
External resistance | 250 Pa. |
Sound power level | 61 dB. Guidance for specification option: Consult manufacturer for details. |
Environment | External. Internal. |
Casing construction | |
Material | Galvanized sheet steel. |
Finish | Self-finish. Polyester powder-coated. Guidance for specification option: Available in standard colours from BS 4800 or RAL ranges. Insert requirements. |
Method of support | Suspended with M10 threaded rod either fixed through the pre-drilled holes within the corner sections or welded lugs. |
Components | |
Dampers | |
Purpose | Bypass damper. Guidance for specification option:
|
Filters | G4 panel air filters. |
Heaters | |
Pre-heaters | Guidance for specification option: Heating coil options are available, consult manufacturer for details. |
Re-heaters | Guidance for specification option: Heating coil options are available, consult manufacturer for details. |
Cooling coils | Guidance for specification option: Cooling coil options are available, consult manufacturer for details. |
Heat recovery | |
Heat recovery equipment | Plate heat exchanger - ERI Corporation PCF-I-3-95-280-T-BR-110-B-SM-HO. |
Supply fan | |
Fan type | Centrifugal fans - GR20V-4IP.Z8.VR. Guidance for specification option:
|
Extract fan | |
Fan type | Centrifugal fans - GR20V-4IP.Z8.VR. Guidance for specification option:
|
Attenuators | Not required. EcoActive 100. Guidance for specification option: 615 x 300 x 200 mm (L x W x H). EcoActive 200. Guidance for specification option: 615 x 400 x 300 mm (L x W x H). EcoActive 300. Guidance for specification option: 615 x 400 x 350 mm (L x W x H). EcoActive 400. Guidance for specification option: 750 x 500 x 400 mm (L x W x H). |
Accessories | Not required. Room sensor - CO₂ and temperature. Guidance for specification option: Wall mounted and wired back to unit. Speed control. Guidance for specification option: 0–10 V signal. |
Integral accessories | Access panel, side (removable panels on quarter turn cam locks and plastic handles). |
Leakage | To EN 16798-3. Manufacturer guidanceLeakage class. |
Building Management System (BMS) connection | Modbus. |
Flow rate | 60 L/s. 100 L/s. Manufacturer guidanceFor ventilation of spaces with occupancies of up to 12 people (based on 8/l/s/p). |
Support frame | Extruded aluminium to BS 1474 - 30 x 30 mm pentapost box section. |
Mullions | Extruded aluminium to BS 1474 – 30 mm mullion joint. |
Controls | Siemens Climatix Controllers, interface units, wall-mounted sensors and room operator units. Guidance for specification option: Consult manufacturer's literature for details and options. |
Dimensions | 1450 x 1000 x 330 mm. |
Unit weight | 134 kg. |
Country of product manufacture | United Kingdom |