NBS Source
I'm a manufacturer

Compare variants

GuideLED SL CG-Line - Self-Contained Safety Luminaire
GuideLED SL CG-Line - Self-Contained Safety Luminaire
GuideLED SL CG-Line - Self-Contained Safety Luminaire

Verified 6 months ago

Eaton Electric

Verified 6 months ago

Eaton Electric

Verified 6 months ago

Eaton Electric
Summary
Emergency pin spot self-contained safety luminaire.
-
-
Application
  • Recessed and surface-mounted safety luminaires.
  • Suitable applications include; healthcare, hotels, offices, cinemas, theatres, museums, commercial centres.
-
-
Description

GuideLed SL is a range of self-contained safety luminaire with a distinctive and innovative design using LED technology. The electronics and long life Li-Ion batteries allow a considerable autonomy in an emergency up to eight hours. This range is proposed with optimal symmetric uniform illumination for open anti-panic spaces, and asymmetric light distribution for escape routes. The use of LEDs, automatic testing and monitoring devices (CGLine+) significantly reduce the operating and maintenance costs of the installation.


Features and benefits:

  • Surface and recessed variants available.
  • Two different optics: for escape route or room illumination.
  • Universal use for maintained or non-maintained solutions and free configurable for 1 h, 3 h or 8 h operation.
  • With environmental-friendly Li-Ion battery technology.
  • Up to 210 lm light output.
  • Li-Ion battery.
  • CGLine+ technology.
  • Degree of protection IP41.
-
-
Color
White
-
-
Material
Polycarbonate, Steel, Aluminium
-
-
Shape
Square
-
-
Length
195 mm
-
-
Width
195 mm
-
-
Height
40 mm
-
-
SKU Code
40071353275, 40071353274, 40071353279, 40071353278, 40071353280, 40071353282
-
-

Specification

Classification data
Standard
To BS EN 60598-2-22.
-
-
Third-party certification
ENEC mark.
-
-
Luminaire description
Recessed luminaire with asymmetric optics for exit route lighting.
-
-
Classification
-
-
-
Electric shock
Class I.
-
-
Ingress protection (minimum)
IP41.
-
-
Circumstances of use
Normal.
-
-
Impact protection (minimum)
IK03.
-
-
Controlgear position
Integral within luminaire.
-
-
Internal fuse
Not required.
-
-
Nominal voltage
230 V a.c.
-
-
LED luminaires
-
-
-
Wattage
6.7 W.
-
-
Emergency version
-
-
-
Standard
To BS EN 60598-2-22.
-
-
Classification
-
-
-
Type
X.
-
-
Mode of operation
0., 1.
-
-
Duration of emergency mode (minimum)
60.
-
-

Additional properties

Testing
CGLine+.
-
-
Luminous flux
210 lm.
-
-
Batteries
Lithium ion battery, 3.7 V/ 4 Ah.
-
-
Housing
White polycarbonate.
Aluminium reflector (heat sink).
Module housing with steel sheet.
-
-
Housing colour
White.
-
-
Dimensions
195 x 195 x 40 mm.
-
-
Mounting
Recessed mounting.
-
-