NBS Source
I'm a manufacturer
Compare variants

GuideLED SL CG-Line - Self-Contained Safety Luminaire

Verified by manufacturer 4 months ago

GuideLed SL 13811 CGLine+ - 40071353275

Eaton Electric Variant:

Emergency pin spot self-contained safety luminaire.

Jump to:
01753 608 700 Website

Application

  • Recessed and surface-mounted safety luminaires.
  • Suitable applications include; healthcare, hotels, offices, cinemas, theatres, museums, commercial centres.

Description

GuideLed SL is a range of self-contained safety luminaire with a distinctive and innovative design using LED technology. The electronics and long life Li-Ion batteries allow a considerable autonomy in an emergency up to eight hours. This range is proposed with optimal symmetric uniform illumination for open anti-panic spaces, and asymmetric light distribution for escape routes. The use of LEDs, automatic testing and monitoring devices (CGLine+) significantly reduce the operating and maintenance costs of the installation.


Features and benefits:

  • Surface and recessed variants available.
  • Two different optics: for escape route or room illumination.
  • Universal use for maintained or non-maintained solutions and free configurable for 1 h, 3 h or 8 h operation.
  • With environmental-friendly Li-Ion battery technology.
  • Up to 210 lm light output.
  • Li-Ion battery.
  • CGLine+ technology.
  • Degree of protection IP41.

General information

Color

White

Material

Polycarbonate

Steel

Aluminium

Shape

Square

Length

195 mm

Width

195 mm

Height

40 mm

Uniclass

Pr_70_70_48_85 Surface luminairesPrimary
Pr_70_70_48_71 Recessed luminaires
Pr_70_70_48_25 Emergency luminaires

CAWS

V90/530 Self-contained emergency luminaires

V90/510 General-purpose luminaires

V90/510 General purpose luminaires

V90/510 Luminaires

Specification data - Surface luminaires

Standard

To BS EN 60598-2-22.

Third-party certification

ENEC mark.

Luminaire description

Recessed luminaire with asymmetric optics for exit route lighting.

Classification

-

Electric shock

Class I.

Ingress protection (minimum)

IP41.

Circumstances of use

Normal.

Impact protection (minimum)

IK03.

Controlgear position

Integral within luminaire.

Internal fuse

Not required.

Nominal voltage

230 V a.c.

Guidance for specification option:

50/60 Hz.

LED luminaires

-

Wattage

6.7 W.

Guidance for specification option:

6.9 VA.

Emergency version

-

Standard

To BS EN 60598-2-22.

Classification

-

Type

X.

Mode of operation

0.

1.

Duration of emergency mode (minimum)

60.

Guidance for specification option:

Selectable emergency duration of 1 h, 3 h or 8 h.

Testing

CGLine+.

Manufacturer guidance

Testing system.

Luminous flux

210 lm.

Batteries

Lithium ion battery, 3.7 V/ 4 Ah.

Housing

White polycarbonate.
Aluminium reflector (heat sink).
Module housing with steel sheet.

Housing colour

White.

Dimensions

195 x 195 x 40 mm.

Manufacturer guidance

Length x width x height.

Mounting

Recessed mounting.

Literature

GuideLED SL CG-Line

GuideLED SL CG-Line