HRV Q Plus (MVHR) - Mechanical Ventilation w/ Heat Recovery
HRV Q Plus (MVHR) - Mechanical Ventilation w/ Heat Recovery
HRV Q Plus (MVHR) - Mechanical Ventilation w/ Heat Recovery

Verified 24 days ago

Titon

Verified 24 days ago

Titon

Verified 24 days ago

Titon
Summary
Range of mechanical ventilation with heat recovery (MVHR) units that work by combining supply and extract air.
Digital objects
-
-
Color
White
-
-
Finish
Powder-coated
-
-
Material
Steel, Polypropylene
-
-
Shape
Rectangle
-
-
Length
285 mm, 353 mm, 477 mm, 533 mm, 600 mm
-
-
Width
600 mm, 752 mm, 1000 mm
-
-
Height
430 mm, 505 mm, 602 mm, 708 mm, 200 mm
-
-
Warranty description
Three year
-
-

Specification

Standards
-
-
-
Performance testing
Tested to BS EN 13141. Conforms to requirements of UK statutory Building Regulations and Technical Standards for Ventilation and BRE 398. SAP Appendix Q tested. Exceeds requirements of Building Regulations Approved Document L (England & Wales). EU RoHS Directive compliant. Conforms to requirements of EC council directives relating to Electromagnetic Compatibility and Electrical Safety: 2006/95/EC (LVD), 2004/108/EC (EMC).
-
-
Safety
To EN 60335-1:2002/A2:2006 and EN 60335-2-80:2003/A1:2004.
-
-
Third-party certification
CE and UKCA marked.
-
-
Duty
Airflow up to 178 L/s (640 m³/h).
-
-
Mounting
Horizontal/ wall.
-
-
Controls
auralite® HRV (TP518)., auralite® HRV (TP519)., aura-t™ HMB (TP539)., aura-t™ B (TP536)., aura-t™ SMART., aura-t™ SMART (B WiFi).
-
-
Accessories
-
-
-

Additional properties

Dimensions
Width x height x depth (excluding bracket): 600 x 430 x 285 mm.
-
-
Weight
16 kg.
-
-
Materials
Housing: Zintec sheet steel.
Internals: Expanded polypropylene (EPP).
Heat exchanger: Polystyrene.
Internal insulation: Closed cell foamed Nitrile rubber, class 0 fire rating.
Standard filters: Grade ISO Coarse 55% (G3) synthetic filters.
-
-
Electrical
Electrical: 230 V, 50/ 60 Hz, 3 A fuse.
-
-
Ducting
125 mm diameter.
-
-
Performance
Maximum number of kitchen and wet rooms: Four.
Heat recovery: 91.
Specific fan power (SFP): 0.59 W/L/s.
Sound level: 23 dB.
-
-
Colour/ Finish
White paint, RAL 9016 semi-gloss Traffic White.
-
-
Model
TP406HMB., TP416B.
-
-
Configuration
Right hand., Left hand.
-
-
Options
N/A.
-
-

Sustainability data

Country of material origin
United Kingdom
-
-
Country of product manufacture
United Kingdom
-
-
Material
Steel, Polypropylene
-
-
Manufacturing plant location
Falconer Rd, Haverhill CB9, UK
-
-
Expected Life
12 year
-
-