NBS Source
I'm a manufacturer

Compare variants

Fire Protection FIRETEX® Platinum - Fire Protection Coating
Fire Protection FIRETEX® Platinum - Fire Protection Coating
Fire Protection FIRETEX® Platinum - Fire Protection Coating

Verified 2 days ago

Sherwin-Williams

Verified 2 days ago

Sherwin-Williams

Verified 2 days ago

Sherwin-Williams
Summary
A solvent and Halogen-free, 100% solids, two pack, modified epoxy based intumescent fire protection coating.
-
-
Application

Applied directly on to blast cleaned steel surfaces by airless spray.

-
-
Description

A solvent and halogen-free, 100% solids, two pack, modified epoxy based intumescent fire protection coating for internally or externally exposed structural steel, where it provides highest durability and combined corrosion protection (up to ISO 12944, corrosivity category C5) and fire protection (up to R120).


Features and benefits:


  • Highly resistant to mechanical impact and damage.
  • No primer required
  • Complies with the sustainability requirements of DGNB (level 3).
  • Long life cycle of >25 years.
  • Up to 120 minutes of fire resistance.
  • CE marked.
  • Tested to EN 13381-8, BS 476 part 20-22 and EN 13501-2.
  • Complies with Indoor Air Comfort Gold.
  • Topcoats can be applied to provide final colour as desired.


-
-
Color
Grey
-
-
Finish
Gloss
-
-
Material
Epoxy
-
-
Shape
Formless
-
-
Length
Bespoke
-
-
Width
Bespoke
-
-
Height
Bespoke
-
-
Warranty description
25 year
-
-

Specification

Composition
Epoxy-borne.
-
-
Colour
Light grey.
-
-

Additional properties

Flash point
>101°C (base and hardener).
-
-
Density
1.3 kg/L.
-
-
Application temperature
10–40°C.
-
-
Abrasion resistance
To ISO 5470-1, ~65 mg/ 1000 R.
-
-
CompressiveStrength
To ISO 604, ~45 MPa.
-
-
TensileStrength
To ISO 527-2, ~10 MPa.
-
-
Adhesion strength
To EN ISO 4624, ~10 N/mm².
-
-
Coverage
0.77 m²/kg will cover 1.00 m²/L.
-
-
Drying time
Eight hours to touch (at 20°C); 24 hours to handle (at 20°C).
-
-
Fire resistance
R120.
-
-