NBS Source
I'm a manufacturer
Compare variants

Fire Protection FIRETEX® Platinum - Fire Protection Coating

Verified by manufacturer 18 days ago

FIRETEX® Platinum-30

Sherwin-Williams Variant:

A solvent and Halogen-free, 100% solids, two pack, modified epoxy based intumescent fire protection coating.

Jump to:
+44 (0)1204 521771 Website

Application

Applied directly on to blast cleaned steel surfaces by airless spray.

Description

A solvent and halogen-free, 100% solids, two pack, modified epoxy based intumescent fire protection coating for internally or externally exposed structural steel, where it provides highest durability and combined corrosion protection (up to ISO 12944, corrosivity category C5) and fire protection (up to R120).


Features and benefits:


  • Highly resistant to mechanical impact and damage.
  • No primer required
  • Complies with the sustainability requirements of DGNB (level 3).
  • Long life cycle of >25 years.
  • Up to 120 minutes of fire resistance.
  • CE marked.
  • Tested to EN 13381-8, BS 476 part 20-22 and EN 13501-2.
  • Complies with Indoor Air Comfort Gold.
  • Topcoats can be applied to provide final colour as desired.


General information

Color

Grey

Finish

Gloss

Material

Epoxy

Shape

Formless

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

25 year

Uniclass

Pr_35_31_68_43 Intumescent protective coatingsPrimary

CAWS

M61/150 Off-site coating to unprimed steel

M61/160 Off-site coating to primed steel

M61/170 Off-site coating to galvanized steel

G10/640 Shop painting

G10/660 Shop plus site painting

Specification data - Intumescent protective coatings

Composition

Epoxy-borne.

Colour

Light grey.

Flash point

>101°C (base and hardener).

Density

1.3 kg/L.

Application temperature

10–40°C.

Abrasion resistance

To ISO 5470-1, ~65 mg/ 1000 R.

CompressiveStrength

To ISO 604, ~45 MPa.

TensileStrength

To ISO 527-2, ~10 MPa.

Adhesion strength

To EN ISO 4624, ~10 N/mm².

Coverage

0.77 m²/kg will cover 1.00 m²/L.

Guidance for specification option:

This figure makes no allowance for surface profile, uneven application, overspray or losses in containers and equipment. 

Drying time

Eight hours to touch (at 20°C); 24 hours to handle (at 20°C).

Fire resistance

R30.

Similar products from Sherwin-Williams

Fire Protection FIRETEX® FX2003

Fire Protection FIRETEX® FX2003

Fire Protection FIRETEX® FX5062

Fire Protection FIRETEX® FX5062

Fire Protection FIRETEX® FX5090

Fire Protection FIRETEX® FX5090

Fire Protection FIRETEX® FX6002

Fire Protection FIRETEX® FX6002

Fire Protection FIRETEX® FX6010

Fire Protection FIRETEX® FX6010

Fire Protection FIRETEX® M71V2

Fire Protection FIRETEX® M71V2