NBS Source
I'm a manufacturer

Application

WWS 100 is specifically designed as a room sensor in NV Embedded® solutions.

Description

Indoor sensor for air quality monitoring by means of temperature, CO2 level and relative humidity measurement. Typically, one sensor per room/zone is used but multiple sensors can be used in the same room/zone if e.g. minimum, maximum and mean values are requested. In addition to sensor functionalities, the unit also has a push-button for simultaneous operation of all windows or selected motor groups in the room/zone; e.g. close or open all windows.


The sensor is connected to a WindowMaster control unit type WCC 310 PLUS, WCC 320 PLUS, WSC 310 PLUS or WSC 320 PLUS via WSK-Link™. Up to 15 sensors can be connected to a control unit.


Features and benefits:

  • Measures the air quality through temperature, CO2 level and relative humidity measurements.
  • Measurements will be sent directly to the controller via WSK-Link™.  

General information

Color

White

Guidance for specification option:

Studio white (corresponding to RAL 9016).

Material

Plastic

Shape

Rectangle

Length

24 mm

Width

83 mm

Height

114 mm

Uniclass

Pr_75_50_76_03 Air temperature sensorsPrimary
Pr_75_50_76_02 Air quality sensors

CAWS

U90/560 Sensors, humidity

U90/560 Sensors, humidity

U90/550 Sensors, air quality

U90/550 Sensors, air quality

U90/580 Sensors, thermal

U90/580 Sensors, thermal

Specification data - Air temperature sensors

Application

Room.

Range

CO2: 400–2000 ppm; Temperature: 0–50°C; Relative humidity: 0–100%.

Accuracy

CO2: +/-150 ppm during product life cycle at 25°C and 950–1050 hPa.
Temperature: +/-0.5°C at 25°C and +/-1°C at 50°C.
Relative humidity: +/-3% at 25°C.

Guidance for specification option:

Factory calibrated for higher than ±50 ppm at 600 ppm and 1000 ppm. Auto-calibration using ABC logic™

Equipment interconnectivity

-

Wired

WSK-Link™, via MotorController type WCC 310 P.

WSK-Link™, via MotorController type WCC 320 P.

WSK-Link™, via smoke control panel type WSC 310 P.

WSK-Link™, via smoke control panel type WSC 320 P.

Ingress protection (IP) rating

IP20.

Guidance for specification option:

Class III (SELV/PELF).

Power consumption

2 mA.

Guidance for specification option:

Power supply via WSK-Link™.

Literature

WWS 100 Data Sheet

WWS 100 Data Sheet

Similar products from WindowMaster Control Systems Ltd

WOT 100 - Outdoor temperature sensor

WOT 100 - Outdoor temperature sensor